Stability limits and enhancement techniques

Short answer

Steady state stability is the ability to stay in synchronism under small gradual load changes; its limit is Pmax=EV/X at δ=90°. Transient stability is the ability after a large sudden disturbance; its lower limit depends on fault severity and clearing time. Enhancing techniques include high-speed fault clearing, reducing transfer reactance, single-pole reclosing, fast excitation, fast valving, braking resistors, and FACTS devices.

What do you mean by steady state and transient stability and their limits in power system? Discuss the techniques for enhancing the transient stability of a power system.

Power system stability is the ability of a power system to return to a normal (synchronous) operating condition after being subjected to a disturbance.

  • Steady state stability is the ability of the system to remain in synchronism when subjected to small and gradual changes in load (or generation). The maximum power that can be transmitted through a point without loss of synchronism under such slow changes is the steady state stability limit. For a machine connected to an infinite bus through reactance XX:
Pmax=EVX(at δ=90∘)P_{max} = \frac{EV}{X} \quad (\text{at } \delta = 90^\circ)
  • Transient stability is the ability of the system to remain in synchronism after a large and sudden disturbance such as a fault, loss of a line, sudden loss of large load or generation. It is studied over the first swing (about 1 s). The maximum power that can be transmitted while the system remains stable after a specified large disturbance is the transient stability limit. It is always lower than the steady state limit and depends on the type, location and clearing time of the disturbance.

Limits for a machine on an infinite bus

 Pe
  ^      steady state limit EV/X
  |          .-''-.
  |        .'      '.
  |------.'---------'.---- transient limit
  |     /             \    (lower; depends on fault)
  |    /               \
  +---+--------+--------+--> delta
      0       90       180
  • Steady state limit: Pss=EV/XP_{ss} = EV/X; operation is stable only where dPe/dδ>0dP_e/d\delta > 0, i.e. δ<90∘\delta < 90^\circ.
  • Transient limit: the largest PmP_m for which, after the given fault and clearing time, the equal area condition A1=A2A_1 = A_2 can still be met.

Techniques for enhancing transient stability

MethodHow it helps
High-speed fault clearing (fast relays, 2-3 cycle breakers)Shortens the time of acceleration, reducing area A1A_1; the most effective method
Reduction of transfer reactance (parallel lines, bundled conductors, series capacitors, low-reactance transformers)Raises Pmax=EV/XP_{max} = EV/X, giving larger decelerating area
Single-pole (independent pole) switching and auto-reclosingOnly the faulted phase is opened (most faults are L-G); power still flows on healthy phases, and the line is reclosed quickly
Fast excitation systems (high-gain static exciters, field forcing) with PSSRaises EE during the fault and after, increasing power transfer
Fast valving / turbine bypassRapidly reduces PmP_m during the fault, reducing acceleration
Braking resistorsResistors switched in at the generator bus absorb power during the fault, decelerating the rotor
Generator tripping / load sheddingRemoving some generation (or load) restores the balance of PmP_m and PeP_e
Higher inertia constant HHSlower rise of δ\delta, giving more time to clear the fault
Higher system voltage and intermediate switching stationsIncrease PmaxP_{max}; switching stations mean only a short section of line is lost
Neutral grounding through impedanceLimits earth-fault effect on power transfer during L-G faults
HVDC links and FACTS (SVC, STATCOM, TCSC)Fast control of power flow and voltage support