Equal area criterion for transient stability
Short answer
Equal area criterion states a single machine-infinite bus system is transiently stable if the accelerating area (where Pm > Pe) equals the decelerating area (where Pe > Pm) on the power-angle curve. Derived by integrating the swing equation: ∫(Pm-Pe)dδ = 0 from δ0 to δmax. Stability requires fault clearing before critical clearing angle where areas just balance.
Explain the Equal area criterion (concept) to study (evaluate) the transient stability of a single machine system connected to infinite bus with proper mathematical aids and diagram.
The equal area criterion (EAC) is a graphical method to check the transient stability of a single machine connected to an infinite bus (or of two machines) without solving the swing equation step by step. It states that the system is stable if, after a disturbance, the area of accelerating energy under the power-angle curve can be balanced by an equal area of decelerating energy.
Basis
For a machine connected to an infinite bus, the swing equation (in pu, resistance and damping neglected) is
Multiplying both sides by :
Integrating from the initial angle (where , the rotor runs at synchronous speed):
For the machine to be stable, the rotor angle must stop increasing at some maximum angle, i.e. at :
This means the area under the – curve must be zero: the accelerating area (where ) must be equal to the decelerating area (where ):
Power-angle diagram
Pe
^ Pmax1 sin d (pre-fault)
| .-''-.
| .' .--. '. Pmax3 sin d
| / .' A2 '. \ (post-fault)
Pm-------+-+-------+--\------
| /|A1| \ \
| / |..|..... \ \ Pmax2 sin d
+----+--+--+--------+--+--> d
0 d0 dc dmax 180
A1: accelerating area, A2: decelerating area
Applying it to a fault (sudden disturbance)
- Before the fault: the machine runs at , where .
- During the fault: the transfer reactance rises, the power curve drops to ( for a fault at the generator bus). Since , the rotor accelerates and increases. The energy gained is area .
- Fault cleared at : the post-fault curve applies. Now , so the rotor decelerates, but keeps increasing until the kinetic energy is given back. This is area .
- Stability test: the system is stable if can become equal to before reaches . The rotor then swings back and oscillates about the new operating point. If the available , the machine loses synchronism.
Critical clearing angle
The largest clearing angle for which just holds (with reaching exactly ) is the critical clearing angle:
For a fault at the generator terminals with no change in network (, , ):
and, since during the fault, the critical clearing time is
Assumptions and limitation
- Mechanical input constant during the transient; damping and resistance neglected.
- Machine represented by a constant voltage behind transient reactance.
- Valid only for one machine against an infinite bus (or two machines); for multi-machine systems, numerical solution of swing equations is needed.
Example: with pu and pu, ; for a terminal fault .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Voltage stability; transient study assumptions · Power System Analysis II, chapter 6
- EAC for a two machine system · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Methods of improving transient stability · Power System Analysis II, chapter 6 · asked 3×
- Proper vs improper handoff; cellular concept N = 7 · Wireless Communication, chapter 2
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Infinite bus and advantages of HVDC · Power System Analysis I, chapter 1
- Limitations of single bus system · Computer Organization and Architecture, chapter 1 · asked 2×