Short answer

Steady-state: frequency deviation Δf = -ΔP_L/(D+1/R), load shared per droop. Transient: after load increase, electrical power jumps instantly, mechanical power lags, frequency falls, governor then corrects; hydro power initially dips due to water inertia.

Describe the steady state and transient behavior of a turbine generator coupled system with governor.

A turbine-generator with a speed governor is a closed loop: the governor senses speed and adjusts the gate so that mechanical input matches electrical load.

Model and block diagram

Rotor and load: ΔΩ(s)=ΔPm−ΔPL2Hs+D\Delta\Omega(s) = \dfrac{\Delta P_m - \Delta P_L}{2Hs + D}

Governor with droop: ΔPv(s)=11+sTg[ΔPref−ΔΩR]\Delta P_v(s) = \dfrac{1}{1+sT_g}\left[\Delta P_{ref} - \dfrac{\Delta\Omega}{R}\right]

Turbine: ΔPm=Gt(s) ΔPv\Delta P_m = G_t(s)\,\Delta P_v with Gt(s)=1−Tws1+0.5TwsG_t(s) = \dfrac{1 - T_w s}{1+0.5T_w s} for hydro.

 dPref +      +-------+ dPv +-------+ dPm
 ---->(+)---->|   1   |---->|turbine|---+
       ^ -    |1+sTg  |     | Gt(s) |   |
       |      +-------+     +-------+   v
    +-----+                   -dPL --->(+)
    | 1/R |                             |
    +-----+      +-----------+          |
       ^     dw  |     1     |          |
       +---------|  2Hs + D  |<---------+
                 +-----------+

Steady state behaviour

With ΔPref=0\Delta P_{ref} = 0 and a step load ΔPL\Delta P_L, the closed loop gives

ΔΩ(s)ΔPL(s)=−12Hs+D+Gt(s)R(1+sTg)\frac{\Delta\Omega(s)}{\Delta P_L(s)} = \frac{-1}{2Hs + D + \dfrac{G_t(s)}{R(1+sT_g)}}

Using the final value theorem (Gt(0)=1G_t(0) = 1):

Δωss=−ΔPLD+1R=−ΔPLβ\Delta\omega_{ss} = \frac{-\Delta P_L}{D + \frac{1}{R}} = \frac{-\Delta P_L}{\beta}

where β=D+1/R\beta = D + 1/R is the area frequency response characteristic. Since 1/R≫D1/R \gg D (e.g. R=0.05R = 0.05 gives 1/R=201/R = 20), the governor reduces the frequency error about 20 times compared with no governor.

  • Speed-power relation: ΔPm=ΔPref−Δω/R\Delta P_m = \Delta P_{ref} - \Delta\omega/R. This is the droop line: as load rises, speed falls in proportion.
  • Units in parallel share a load change in proportion to 1/R1/R (i.e. to rating, if all have the same per-unit droop).
  • Changing ΔPref\Delta P_{ref} shifts the droop line up or down; this restores frequency to nominal (secondary control).

Transient behaviour

When a load ΔPL\Delta P_L is suddenly added:

  1. Instant t=0+t = 0^+: the electrical output PeP_e rises at once by ΔPL\Delta P_L, because the generator must supply the connected load immediately. The mechanical input PmP_m cannot change instantly (gate and water need time).
  2. Deceleration: the deficit Pe−PmP_e - P_m is supplied from the kinetic energy of the rotor, so speed starts to fall with slope −ΔPL/2H-\Delta P_L/2H.
  3. Load damping: as speed falls, frequency-sensitive load drops by DΔωD\Delta\omega, so PeP_e comes down slightly from its initial jump.
  4. Governor action: the speed fall is sensed; through the droop 1/R1/R the governor opens the gate. For a hydro turbine, PmP_m first dips (water inertia, non-minimum phase) and then rises.
  5. Recovery: when PmP_m exceeds PeP_e, the rotor accelerates and the fall in speed is arrested. After some oscillation, Pm=PeP_m = P_e and speed settles at a new, lower value.

Steady state, from the block diagram (s→0s \to 0):

Δωss=−ΔPLD+1R,ΔPm,ss=ΔPe,ss=ΔPL+D Δωss\Delta\omega_{ss} = \frac{-\Delta P_L}{D + \frac{1}{R}}, \qquad \Delta P_{m,ss} = \Delta P_{e,ss} = \Delta P_L + D\,\Delta\omega_{ss}
 power
     |   Pe
 P0+ |   ._____
 dPL |   |     '--.________ Pm = Pe (final)
     |   |         _.-'
     |   |      _.'  Pm
  P0 |---'.   .'
     |     '.'  (hydro: Pm dips first)
     +---------------------------> t
 speed
     |----.
     |     \        .--------
     |      '._  _.'   dw_ss = -dPL/(D+1/R)
     |         ''
     +---------------------------> t
  • Electrical power PeP_e: jumps by ΔPL\Delta P_L at once, then reduces slightly as frequency falls (load damping) and settles at ΔPL+DΔωss\Delta P_L + D\Delta\omega_{ss}.
  • Mechanical power PmP_m: starts at the old value (dips first in a hydro unit), rises with the governor and turbine time constants, overshoots slightly, and settles equal to PeP_e.
  • Speed: falls, reaches a minimum (frequency nadir), recovers partly and settles at a lower value Δωss\Delta\omega_{ss} fixed by the droop. With an isochronous governor (R→0R \to 0) speed would return to nominal. Supplementary control (load reference change) is then used to bring the frequency back to 50 Hz.