Isochronous generator transient response
Short answer
An isochronous generator uses an integral governor (zero droop) to maintain constant frequency. Following a step load increase, speed drops, integral action increases prime mover power, and speed exactly recovers with zero steady-state frequency error.
What do you mean by Isochronous generator? Describe its transient response for a step increase in load.
An isochronous generator is a generating unit whose governor is isochronous (integral type, zero droop). It keeps the speed and frequency exactly at the set value for any load within its rating. It is used for a single unit supplying an isolated load, or for one unit that controls frequency in a small system.
Governor law: , so the gate keeps moving as long as there is any speed error.
Transient response to a step increase in load
power
P0+dPL .________________ Pe
| __.-- Pm -> Pe
| _.'
P0 ______|__/ (Pm)
t = 0
speed
w0 ______. .---- w0 (restored)
\ .'
'.____.-'
t = 0 time
- At the electrical output jumps by ; is unchanged, so the rotor decelerates and speed falls (slope ).
- The integral governor opens the gate; rises (a hydro turbine first dips a little).
- When the rotor speeds up again. Because the integrator acts until the error is zero, the speed returns exactly to .
- Final state: and . Frequency error is zero, unlike a droop governor which leaves .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transient response of turbine-generator with governor · Power Plant Equipment, chapter 2 · asked 3×
- Speed response without governor and isochronous governor · Power Plant Equipment, chapter 2 · asked 2×
- Water turbine response to step gate change · Power Plant Equipment, chapter 2 · asked 2×
- Isochronous governor and speed droop model · Power Plant Equipment, chapter 2
- Steady state and transient behaviour with governor · Power Plant Equipment, chapter 2 · asked 2×
- Ideal LPF impulse and step response · Signals and Systems, chapter 5 · asked 5×
- Step response of RC filter · Signals and Systems, chapter 5 · asked 3×
- Closed vs open loop step response analytically · Control Systems, chapter 1 · asked 2×
- Unit step response for h(t) = exp(-at) · Data Communication, chapter 2