Speed response without governor and isochronous governor
Short answer
Without governor, the speed response transfer function is ΔΩ(s)/ΔPL(s) = -1/(2Hs+D), leading to a steady-state speed drop -ΔPL/D. An isochronous governor uses an integrator (K/s) in the forward path, forcing the steady-state speed error to zero by adjusting gate position until Pm equals PL.
Derive the transfer function for speed response for load change in turbine-generator set in the absence of governor. Also, explain how isochronous governor can be incorporated together with turbine-generator with block diagram.
Transfer function without governor
Without a governor, the turbine gate is fixed, so and the speed is decided only by rotor inertia and load damping.
Inertia (rotating mass): for small changes, in per unit, the swing equation is
where = inertia constant (s), = speed deviation (pu). Taking the Laplace transform,
Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So
where = non-frequency-sensitive load change and = load damping constant (% change in load per % change in frequency, typically 1–2).
Substituting,
With :
dPm=0 + +--------------+
------>(+)->| 1 |----+--> d(omega)
^ - | 2Hs + D | |
| +--------------+ |
dPL
For a step load :
The speed falls exponentially with time constant and settles at , which is a large error because is small.
Incorporating an isochronous governor
An isochronous (constant speed) governor uses integral control. It measures speed, compares with the reference, and integrates the error to move the gate:
The gate keeps moving as long as there is any speed error, so speed returns exactly to the set value.
dPL
| -
+-------+ dPm v +-----------+
|turbine|--------------->(+)---->| 1/(2Hs+D) |--+--> dw
| Gt(s) | + +-----------+ |
+-------+ |
^ dY |
+-------+ - |
| K/s |<---(+)<-------------------------------+
+-------+ ^ +
| dw_ref = 0
Here is the turbine transfer function (for hydro, ).
Working: a load rise makes speed fall; the integrator output grows, gates open, rises above , the rotor accelerates and speed comes back to the reference. In steady state and .
The isochronous governor works well for a single unit supplying an isolated load. It cannot be used on several units in parallel, because each would try to fix the frequency at its own set point and they would fight for the load; for that, speed droop is added.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transient response of turbine-generator with governor · Power Plant Equipment, chapter 2 · asked 3×
- Isochronous governor and speed droop model · Power Plant Equipment, chapter 2
- Speed control by inertia and load damping · Power Plant Equipment, chapter 2 · asked 6×
- Isochronous generator transient response · Power Plant Equipment, chapter 2
- Water turbine response to step gate change · Power Plant Equipment, chapter 2 · asked 2×
- Isochronous governor and parallel operation problem · Power Plant Equipment, chapter 2 · asked 6×
- Armature-controlled DC motor transfer function and block diagram · Control Systems, chapter 2
- PID controller block diagram, transfer function, characteristics · Control Systems, chapter 7
- Impulse response, transfer function and distortionless transmission · Communication Systems, chapter 1
- DMA controller block diagram and transfer · Computer Organization and Architecture, chapter 7 · asked 6×