Isochronous governor and parallel operation problem
Short answer
An isochronous governor maintains exactly constant speed for all loads using integral control, eliminating steady-state frequency error. It is unsuitable for parallel units because each tries to enforce its own setpoint, causing fighting and unstable load sharing; only one unit may run isochronous, and others must use speed droop.
What is isochronous governor? Explain with its closed loop control system. Why it is not suitable for two generating units operating in parallel?
An isochronous governor is a speed governor that keeps the turbine speed (frequency) exactly constant at the set value for every load. "Isochronous" means "same speed". It uses integral action: the gate keeps moving as long as there is a speed error.
Closed loop control system
w_ref + error +------+ dY +-------+ dPm
---->(+)-------->| K/s |--->|turbine|---+
^ - +------+ +-------+ |
| v
| -dPL -->(+)
| +-----------+ |
+------| 1/(2Hs+D) |<--------------+
speed +-----------+
Governor law:
Operation:
- Load increases, , so the rotor slows down.
- The speed error is integrated; the integrator output opens the gate.
- increases; once it exceeds the rotor accelerates back.
- The integrator stops changing only when the error is zero. So in steady state and : zero steady-state frequency error.
speed
w0 |-----. .---------- w0 (restored)
| \ /
| '.___.'
+-------------------------> t
Pm rises until Pm = Pe
Why it is not suitable for units in parallel
- Units in parallel are tied to the same frequency. Each isochronous governor tries to hold the frequency at its own set value.
- The set points can never be exactly equal. If unit 1 is set at 50.01 Hz and unit 2 at 50.00 Hz, unit 1 keeps opening its gate to raise frequency while unit 2 keeps closing, so they fight each other. One unit is driven to full load and the other to zero (or motoring).
- With integral control there is no unique load sharing: the load can be divided in any ratio and drifts. The operating point is not stable.
- Therefore only one unit in a system (or an isolated unit) may run isochronous. Other units use a speed droop characteristic, which gives a definite sharing of load in proportion to .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isochronous governor and speed droop model · Power Plant Equipment, chapter 2
- Speed response without governor and isochronous governor · Power Plant Equipment, chapter 2 · asked 2×
- Define control system and closed loop block roles · Control Systems, chapter 1 · asked 5×
- Closed loop control system block diagram explained · Control Systems, chapter 1 · asked 4×
- Steps to design closed loop control system · Embedded System, chapter 7
- Control system block diagram and closed loop advantages · Control Systems, chapter 1