- 2069 Chaitra · 8 marks
Isochronous governor and speed droop model
Short answer
An isochronous governor uses integral control to hold speed constant, but parallel units with different set points fight and load sharing is unstable. With droop feedback, the governor transfer function is ΔY/ΔΩ = -1/R * 1/(1+sT_G), giving steady-state droop R = -Δω/ΔY.
What do you mean by isochronous governor and explain its operation? Why it is not suitable for multiple number of generating units operating in parallel. Derive the mathematical model of governor with speed droop characteristics.
An isochronous governor keeps the turbine speed constant at its set value for all loads ("isochronous" = same speed). It uses integral control: the gate keeps moving until the speed error is zero.
Operation
w_ref + error +------+ dY +-------+ dPm
---->(+)-------->| K/s |--->|turbine|---+
^ - +------+ +-------+ |
| v
| -dPL -->(+)
| +-----------+ |
+------| 1/(2Hs+D) |<--------------+
speed +-----------+
- A load increase makes , so speed falls.
- The speed error is integrated: . The gate opens and rises.
- The rotor accelerates back. The integrator stops only when the error is zero, so speed returns exactly to , with .
Why not for several units in parallel
- Parallel units run at one common frequency. Each isochronous governor tries to hold the frequency at its own set point.
- Set points are never exactly equal, so the units fight: the one with the higher set point keeps opening and the other keeps closing, until one is at full load and the other at zero or motoring.
- Integral control has no fixed relation between speed and load, so the load sharing is not defined and is unstable. Only one unit in a system can be isochronous; others need droop.
Mathematical model of a governor with speed droop
Droop is obtained by feeding the gate position back through a gain around the integrator (steady-state feedback):
+------+ dY
-dw ---->(+)--->| K/s |---+---> to turbine
^ - +------+ |
| +-----+ |
+-----| R |<---+
+-----+
With no change in load reference:
where is the governor time constant. Including the load reference,
Steady state (): , i.e. (pu). This is the speed droop characteristic: speed falls linearly as output rises. A 5 % droop means a 5 % speed drop gives a 100 % change in gate (output). It gives a unique and stable load sharing between parallel units in proportion to .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isochronous governor and parallel operation problem · Power Plant Equipment, chapter 2 · asked 6×
- Speed response without governor and isochronous governor · Power Plant Equipment, chapter 2 · asked 2×
- Droop calculation: 800 MW and 300 MW units · Power Plant Equipment, chapter 2
- Speed droop in sharing common load · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 MVA and 500 MVA, 4%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Number of Francis/Kaplan units (300 m³/s, 30 m) · Hydropower Engineering, chapter 7
- Random number; problems in generating pseudo-random · Simulation and Modeling, chapter 6
- Number of Kaplan units (380 m³/s, 30 m) · Hydro Power, chapter 7 · asked 2×
- Number of propeller turbine units · Hydro Power, chapter 7