An isochronous governor uses integral control to hold speed constant, but parallel units with different set points fight and load sharing is unstable. With droop feedback, the governor transfer function is ΔY/ΔΩ = -1/R * 1/(1+sT_G), giving steady-state droop R = -Δω/ΔY.

What do you mean by isochronous governor and explain its operation? Why it is not suitable for multiple number of generating units operating in parallel. Derive the mathematical model of governor with speed droop characteristics.

An isochronous governor keeps the turbine speed constant at its set value for all loads ("isochronous" = same speed). It uses integral control: the gate keeps moving until the speed error is zero.

Operation

 w_ref +   error  +------+ dY +-------+ dPm
 ---->(+)-------->| K/s  |--->|turbine|---+
       ^ -        +------+    +-------+   |
       |                                  v
       |                         -dPL -->(+)
       |      +-----------+               |
       +------| 1/(2Hs+D) |<--------------+
        speed +-----------+
  1. A load increase makes Pe>PmP_e > P_m, so speed falls.
  2. The speed error is integrated: ΔY=−KsΔΩ\Delta Y = -\dfrac{K}{s}\Delta\Omega. The gate opens and PmP_m rises.
  3. The rotor accelerates back. The integrator stops only when the error is zero, so speed returns exactly to ωref\omega_{ref}, with ΔPm=ΔPL\Delta P_m = \Delta P_L.

Why not for several units in parallel

  • Parallel units run at one common frequency. Each isochronous governor tries to hold the frequency at its own set point.
  • Set points are never exactly equal, so the units fight: the one with the higher set point keeps opening and the other keeps closing, until one is at full load and the other at zero or motoring.
  • Integral control has no fixed relation between speed and load, so the load sharing is not defined and is unstable. Only one unit in a system can be isochronous; others need droop.

Mathematical model of a governor with speed droop

Droop is obtained by feeding the gate position back through a gain RR around the integrator (steady-state feedback):

                 +------+  dY
 -dw ---->(+)--->| K/s  |---+---> to turbine
           ^ -   +------+   |
           |     +-----+    |
           +-----|  R  |<---+
                 +-----+

With no change in load reference:

ΔY(s)=Ks[−ΔΩ(s)−R ΔY(s)]\Delta Y(s) = \frac{K}{s}\left[-\Delta\Omega(s) - R\,\Delta Y(s)\right] s ΔY=−KΔΩ−KR ΔYΔY(s)(s+KR)=−K ΔΩ(s)ΔY(s)ΔΩ(s)=−Ks+KR=−1R⋅11+sTG\begin{aligned} s\,\Delta Y &= -K\Delta\Omega - KR\,\Delta Y \\ \Delta Y(s)(s + KR) &= -K\,\Delta\Omega(s) \\ \frac{\Delta Y(s)}{\Delta\Omega(s)} &= -\frac{K}{s + KR} = -\frac{1}{R}\cdot\frac{1}{1 + sT_G} \end{aligned}

where TG=1KRT_G = \dfrac{1}{KR} is the governor time constant. Including the load reference,

ΔY(s)=11+sTG[ΔPref(s)−1RΔΩ(s)]\Delta Y(s) = \frac{1}{1 + sT_G}\left[\Delta P_{ref}(s) - \frac{1}{R}\Delta\Omega(s)\right]

Steady state (s→0s \to 0): ΔY=ΔPref−Δω/R\Delta Y = \Delta P_{ref} - \Delta\omega/R, i.e. R=−Δω/ΔYR = -\Delta\omega/\Delta Y (pu). This is the speed droop characteristic: speed falls linearly as output rises. A 5 % droop means a 5 % speed drop gives a 100 % change in gate (output). It gives a unique and stable load sharing between parallel units in proportion to 1/R1/R.