Speed droop in sharing common load
Short answer
Speed droop provides each unit a definite speed-load line, ensuring stable load division. The load change share ratio equals (P_r/R) of the units; equal per-unit droop divides load proportionally to ratings, preventing instability.
Explain the importance of speed droop in sharing common load by two alternator operating in parallel with suitable block diagram and derivation.
Speed droop is the drop in speed (frequency) of a governed unit as its load goes from no load to full load, expressed in per unit of rated speed. It is defined by
A 4 % droop means the frequency falls by 4 % (2 Hz at 50 Hz) from no load to full load. Droop gives every governor a definite speed–load line, so parallel units share a load change in a fixed, stable ratio. Without droop (isochronous governors), parallel units fight each other and the load division is undefined.
Block diagram (two units on a common bus)
+-->[1/R1]--+
| v -
| dPref1->(+)->[Gov1]->[Turb1]--dPm1--+
| v
| -dPL ------->(S)--+
| ^ |
| dPref2->(+)->[Gov2]->[Turb2]--dPm2--+ |
| ^ - v
+-->[1/R2]--+ [1/(2Hs+D)]
| |
+--------------- d(omega) -----------------+
S = summing point: .
Both units see the same frequency deviation because they are synchronised.
Derivation
In steady state, the governor of unit obeys its droop line:
With fixed references ():
The total change must supply the load change:
and the ratio of sharing is
If (same per-unit droop), , i.e. load is shared in proportion to ratings.
f f
f0|\ unit 1 |\ unit 2
| \ | \
f'|--*-----common f'--|---*
| \ | \
+----+---> P1 +-----+---> P2
P1' P2'
Importance
- Gives a unique, stable division of load among parallel units.
- A smaller droop makes a unit "stiffer", so it takes a bigger share of any change.
- Equal per-unit droop on all units makes each carry load proportional to its rating, avoiding overload of small units.
- The frequency drop needed is small (typically 4–5 % droop), and the load reference setting is then used to bring frequency back to nominal.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 600 MVA and 500 MVA, 4%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 20%/10% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 4%/3% droop · Power Plant Equipment, chapter 2
- Droop for capacity sharing: 500 and 250 MW · Power Plant Equipment, chapter 2
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- Load sharing of two transformers in parallel · Electrical Machines, chapter 2
- Companding; DPCM with derivation and block diagram · Communication Systems, chapter 4
- Load sharing of 50 kVA and 25 kVA transformers in parallel · Electrical Machines I, chapter 2