- 2079 Bhadra · 10 marks
Droop calculation: 800 MW and 300 MW units
Short answer
From no-load 51 Hz to full-load lines: stiffness from operating points gives droops. On own ratings, R1 = 2.67%, R2 = 3%. At 50.2 Hz (drop 0.8 Hz from no-load), G1 supplies 480 MW, G2 supplies 160 MW, total 640 MW.
Shows figure below two generators operating in parallel and supplying a load of 800 MW. G1 is rated as 800 MW and G2 is rated as 300 MW. G1 supplies 600 MW and G2 supplies 200 MW and system frequency is 50 Hz. At no-load, they operate at a common frequency of 51 Hz. Calculate droop regulations R1 and R2 of G1 and G2 with respect their ratings. Assume base power = 1000 MW. When the load is decreased below 800 MW, the frequency increases to 50.2 Hz. Calculate the power supplied by each generator at reduced load. [Figure: G1 (800 MW, R1 = ?) supplying P1 = 600 MW and G2 (300 MW, R2 = ?) supplying P2 = 200 MW to a common bus feeding load PL = 800 MW]
The droop line of each unit passes through its no-load point (51 Hz, 0 MW) and its present operating point (50 Hz, given MW). Extending the line to rated output gives the droop.
Frequency drop from no load to present load: Hz.
Stiffness of each unit:
Droop on own ratings
Frequency drop at rated output: G1: Hz; G2: Hz.
Droop on the common base of 1000 MW
Check: : G1 MW ✓, G2 MW ✓.
Load sharing at 50.2 Hz
Frequency drop from no load Hz.
Total load MW, i.e. the load has decreased by 160 MW (G1 sheds 120 MW, G2 sheds 40 MW).
Answer: and on own ratings (3.33 % and 10 % on 1000 MW base). At 50.2 Hz, G1 = 480 MW, G2 = 160 MW (total 640 MW).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 and 300 MW, 51 Hz no-load · Power Plant Equipment, chapter 2
- Load sharing: 600 and 300 MW at 49 Hz · Power Plant Equipment, chapter 2 · asked 4×
- Load sharing: 900 MW and 450 MW generators · Power Plant Equipment, chapter 2
- Load sharing: 600 MVA and 500 MVA, 4%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Two generators 200∠30° and 210∠50° V · Power System Analysis I, chapter 3
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Three-point problem: A 800 m N, C 600 m E (600, 200, 500) · Engineering Geology I, chapter 5 · asked 4×