Transient response of turbine-generator with governor

Short answer

Upon a sudden load increase, electrical power jumps instantly by ΔPL. Speed drops as the deficit is supplied from rotor inertia, then a governor opens the gate; for a hydro turbine, mechanical power initially dips before rising. Speed recovers to a lower steady-state value determined by droop and load damping.

The figure below shows a turbine-generator coupled system with speed governor. Explain the transient responses of electrical power output (Pe), mechanical power input (Pm) and speed due to sudden increase in electrical load by an amount of ΔPL. [Figure: water enters the turbine through a valve controlled by the governor; the turbine (Pm) is coupled to the generator, which delivers Pe to the load]

With a speed governor, the turbine-generator responds to a sudden load increase by first giving up stored kinetic energy and then, through governor action, increasing the water flow until mechanical input again equals electrical output.

System model

Inertia (rotating mass): for small changes, in per unit, the swing equation is

2Hd Δωdt=ΔPm−ΔPe2H\frac{d\,\Delta\omega}{dt} = \Delta P_m - \Delta P_e

where HH = inertia constant (s), Δω\Delta\omega = speed deviation (pu). Taking the Laplace transform,

ΔΩ(s)=12Hs[ΔPm(s)−ΔPe(s)]\Delta\Omega(s) = \frac{1}{2Hs}\big[\Delta P_m(s) - \Delta P_e(s)\big]

Load damping: a composite load has frequency-insensitive parts (lighting, heating) and frequency-sensitive parts (motors). So

ΔPe=ΔPL+D Δω\Delta P_e = \Delta P_L + D\,\Delta\omega

where ΔPL\Delta P_L = non-frequency-sensitive load change and DD = load damping constant (% change in load per % change in frequency, typically 1–2).

Substituting,

2Hs ΔΩ(s)=ΔPm(s)−ΔPL(s)−D ΔΩ(s)ΔΩ(s)=ΔPm(s)−ΔPL(s)2Hs+D\begin{aligned} 2Hs\,\Delta\Omega(s) &= \Delta P_m(s) - \Delta P_L(s) - D\,\Delta\Omega(s) \\ \Delta\Omega(s) &= \frac{\Delta P_m(s) - \Delta P_L(s)}{2Hs + D} \end{aligned}

The governor with speed droop RR gives

ΔPv(s)=11+sTg[ΔPref(s)−1RΔΩ(s)]\Delta P_v(s) = \frac{1}{1 + sT_g}\left[\Delta P_{ref}(s) - \frac{1}{R}\Delta\Omega(s)\right]

and the hydraulic turbine gives

ΔPm(s)ΔPv(s)=1−Tws1+0.5Tws\frac{\Delta P_m(s)}{\Delta P_v(s)} = \frac{1 - T_w s}{1 + 0.5T_w s}
 dPref +      +-------+ dPv +-------+ dPm
 ---->(+)---->|   1   |---->|turbine|---+
       ^ -    |1+sTg  |     | Gt(s) |   |
       |      +-------+     +-------+   v
    +-----+                   -dPL --->(+)
    | 1/R |                             |
    +-----+      +-----------+          |
       ^     dw  |     1     |          |
       +---------|  2Hs + D  |<---------+
                 +-----------+

Transient response to a sudden load increase

When a load ΔPL\Delta P_L is suddenly added:

  1. Instant t=0+t = 0^+: the electrical output PeP_e rises at once by ΔPL\Delta P_L, because the generator must supply the connected load immediately. The mechanical input PmP_m cannot change instantly (gate and water need time).
  2. Deceleration: the deficit Pe−PmP_e - P_m is supplied from the kinetic energy of the rotor, so speed starts to fall with slope −ΔPL/2H-\Delta P_L/2H.
  3. Load damping: as speed falls, frequency-sensitive load drops by DΔωD\Delta\omega, so PeP_e comes down slightly from its initial jump.
  4. Governor action: the speed fall is sensed; through the droop 1/R1/R the governor opens the gate. For a hydro turbine, PmP_m first dips (water inertia, non-minimum phase) and then rises.
  5. Recovery: when PmP_m exceeds PeP_e, the rotor accelerates and the fall in speed is arrested. After some oscillation, Pm=PeP_m = P_e and speed settles at a new, lower value.

Steady state, from the block diagram (s→0s \to 0):

Δωss=−ΔPLD+1R,ΔPm,ss=ΔPe,ss=ΔPL+D Δωss\Delta\omega_{ss} = \frac{-\Delta P_L}{D + \frac{1}{R}}, \qquad \Delta P_{m,ss} = \Delta P_{e,ss} = \Delta P_L + D\,\Delta\omega_{ss}
 power
     |   Pe
 P0+ |   ._____
 dPL |   |     '--.________ Pm = Pe (final)
     |   |         _.-'
     |   |      _.'  Pm
  P0 |---'.   .'
     |     '.'  (hydro: Pm dips first)
     +---------------------------> t
 speed
     |----.
     |     \        .--------
     |      '._  _.'   dw_ss = -dPL/(D+1/R)
     |         ''
     +---------------------------> t
  • Electrical power PeP_e: jumps by ΔPL\Delta P_L at once, then reduces slightly as frequency falls (load damping) and settles at ΔPL+DΔωss\Delta P_L + D\Delta\omega_{ss}.
  • Mechanical power PmP_m: starts at the old value (dips first in a hydro unit), rises with the governor and turbine time constants, overshoots slightly, and settles equal to PeP_e.
  • Speed: falls, reaches a minimum (frequency nadir), recovers partly and settles at a lower value Δωss\Delta\omega_{ss} fixed by the droop. With an isochronous governor (R→0R \to 0) speed would return to nominal. Supplementary control (load reference change) is then used to bring the frequency back to 50 Hz.

Conclusion: inertia limits the initial rate of fall, the governor limits the depth of the fall and brings PmP_m up to match PeP_e, and the droop leaves a small steady frequency error which is removed by changing the load reference.