Head, specific speed and part load in turbine choice

Short answer

Head sets turbine type: Pelton high (above ~300 m), Francis medium (30–300 m), Kaplan low (2–40 m). Specific speed combines N, P, H and fixes runner shape; choose highest synchronous speed satisfying cavitation and runaway limits. Part-load: Pelton/Kaplan have flat efficiency; Francis peaks at 80–90% and is poor below 40–50%, so use multiple units.

Discuss the effect of the following factors in selecting of a turbine for a hydroelectric plant? (i) head (ii) speed and specific speed (iii) part load operation.

Turbine selection depends mainly on head, speed/specific speed and the expected part-load operation.

(i) Head

Head is the first and most important factor because it decides the velocity of water.

Head rangeSuitable turbine
High (above ~300 m, up to 1300 m)Pelton (impulse)
Medium (30–300 m)Francis (reaction)
Low (2–40 m)Kaplan / propeller
Small plants, 3–250 mCrossflow, Turgo
  • High head gives high jet velocity; an impulse turbine with small flow suits it.
  • Low head needs large flow to give the same power, so a large flow-area axial runner (Kaplan) is used.
  • Head variation also matters: Kaplan copes with varying head better than propeller.

(ii) Speed and specific speed

Ns=NPH5/4N_s = \frac{N\sqrt{P}}{H^{5/4}}
  • Specific speed joins head, power and speed into one value that fixes the runner shape: Pelton 10–35, Francis 60–300, Kaplan 300–1000.
  • A higher running speed gives a smaller, cheaper generator (fewer poles, N=120f/pN = 120f/p), so designers prefer the highest speed that is safe.
  • But higher NsN_s means a higher Thoma cavitation coefficient, so the runner must be set lower (more excavation), and the runaway speed is higher.
  • Therefore the speed is chosen as the highest synchronous speed for which cavitation and runaway limits are satisfied.

(iii) Part-load operation

ROR plants often run at part load in the dry season, so the shape of the efficiency curve matters.

 eff
  |   ____________ Pelton/Kaplan (flat)
  |  /    ___
  | /    /   \__ Francis (peaked)
  |/    /       \__ Propeller (sharp)
  +--------------------> % load
  0   25  50  75  100
  • Pelton: efficiency stays high from about 20% to 100% load (flow controlled by needle; multiple jets can be shut).
  • Kaplan: adjustable runner blades and guide vanes keep high efficiency over a wide range.
  • Francis: best efficiency near 80–90% of rated load; falls quickly below about 40–50%, with vibration and cavitation.
  • Propeller (fixed blade): very poor at part load.

If part-load running is expected, choose Pelton/Kaplan, or use several smaller Francis units so each runs near full load.