Swing equation and inertia constant
Short answer
From Newton's law, J d2δm/dt2 = Tm - Te; multiplying by speed and using H = ½Jωs²/S gives (2H/ωs) d2δ/dt2 = Pm - Pe in per unit, or (H/πf)d2δ/dt2 = Pm - Pe. H is stored kinetic energy per MVA; larger H slows rotor acceleration and increases critical clearing time.
Derive an expression for the swing equation of a synchronous machine. Signify the importance of inertia constant in the machine.
The swing equation describes how the rotor angle of a synchronous machine changes when the mechanical input and electrical output are not balanced.
Derivation
Consider the rotor of a synchronous generator. Let
- = moment of inertia of rotor and turbine (kg·m²)
- = angular position of the rotor with respect to a stationary axis (mech. rad)
- = mechanical (shaft) torque, = electromagnetic torque (N·m)
Step 1: Newton's law of rotation. Accelerating torque = moment of inertia × angular acceleration:
Step 2: Measure angle from a synchronously rotating frame. The rotor angle is the angle of the rotor relative to a reference axis rotating at synchronous speed :
so
Step 3: Convert torque to power. Multiply by the rotor speed (power = torque × speed):
is the angular momentum (inertia constant). Since the speed changes very little during a swing, and is taken as constant:
Step 4: Introduce the inertia constant . is the stored kinetic energy at synchronous speed per MVA rating :
Substituting and dividing by :
Step 5: Use electrical angle. For a machine with poles, and , so :
with in electrical radians and . If is in electrical degrees, .
For a machine connected to an infinite bus through reactance , , so
This is the swing equation. It is a second-order non-linear differential equation; its solution describes how the rotor swings after a disturbance. If damping is included, a term is added on the left.
Importance of the inertia constant
- Rate of rotor swing: from , a larger gives a smaller acceleration for the same power imbalance, so rises more slowly after a fault.
- Critical clearing time: for a terminal fault , so . Higher allows more time for breakers to clear the fault.
- Narrow range: lies in a narrow range for each machine type (about 2-9 s), e.g. turbo-alternators 4-9 s, hydro generators 2-4 s, so typical values can be assumed when data are missing.
- Equivalent machine: machines swinging together can be combined: .
- Frequency response: also decides how fast the system frequency falls after loss of generation.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Swing equation of synchronous machine · Power System Analysis II, chapter 6
- Equivalent swing equation, coherent machines · Power System Analysis II, chapter 6
- Stability definitions and swing equation from dynamics · Power System Analysis II, chapter 6
- Stability classification and swing equation · Power System Analysis II, chapter 6
- Swing equation and swing curve · Power System Analysis II, chapter 6
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Derive expression for tile drain spacing · Irrigation and Drainage Engineering, chapter 9 · asked 8×
- Construction of synchronous machine and rotor types · Electric Machines II, chapter 1 · asked 2×
- Synchronous generator principle and EMF equation · Electric Machines II, chapter 1
- Derive development length expression · Design of RCC Structure, chapter 6 · asked 6×