- 2076 Asoj · 8 marks
Sedimentation tank 6 m x 18 m x 3 m, 4 ML/day
Short answer
Detention period is 1.94 h and surface overflow rate is 37.04 m³/m²/day. The tank is acceptable with coagulation, but for plain sedimentation the detention time is slightly low and the overflow rate is high.
In a sedimentation tank (dimensions: 6 m wide, 18 m long and 3 m depth), 4 million litres of water passes per day. Calculate (a) detention period and (b) surface overflow rate. Check the values with standard range.
Data
Width m, length m, depth m, flow ML/day m³/day.
(a) Detention period
(b) Surface overflow rate
Check with the standard range
Horizontal velocity m/day m/min (the limit is 0.3 m/min; OK).
| Item | Computed | Usual range (plain sedimentation) | Remark |
|---|---|---|---|
| Detention period | 1.94 h | 2 to 4 h (up to 6 h for plain tanks) | Just below 2 h, slightly low |
| SOR | 37.0 m³/m²/day | 15 to 30 m³/m²/day (plain); 30 to 40 (with coagulation) | Above the plain range, within that for coagulated water |
| Velocity | 0.154 m/min | below 0.3 m/min | Satisfactory |
| Depth | 3 m | 2.5 to 5 m | Satisfactory |
| L : B | 3 : 1 | 3:1 to 5:1 | Satisfactory |
Answer: detention period = 1.94 h; SOR = 37.04 m³/m²/day. The tank is satisfactory only if coagulation is used; for plain sedimentation the tank is slightly small (detention a little low and SOR high), so the area should be increased.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Rectangular sedimentation tank, 8x10^6 L/day · Water Supply Engineering, chapter 6
- Rectangular sedimentation tank, 9 million L peak demand · Water Supply Engineering, chapter 6
- Rectangular sedimentation tank for 3000 persons · Water Supply Engineering, chapter 6
- Rectangular sedimentation tank for 10 MLD · Water Supply Engineering, chapter 6
- Storage tank capacity and water level, 20000 L/day · Water Supply Engineering, chapter 7 · asked 2×
- Disinfection factors; bleaching powder 5 ML/day · Water Supply Engineering, chapter 6
- Standard rate filter, 3 MLD, 175 mg/l, NRC · Sanitary Engineering, chapter 7
- Standard rate trickling filter, 1.2 MLD, NRC · Sanitary Engineering, chapter 7 · asked 3×
- Standard rate trickling filter, 3 MLD, 300 mg/l · Sanitary Engineering, chapter 7 · asked 3×
- Sludge volume from sedimentation tank, 10 MLD · Sanitary Engineering, chapter 8