Slow sand filter construction and design

Short answer

A slow sand filter consists of a rectangular tank with a supernatant water layer 1.0–1.5 m deep over a fine sand bed (0.9–1.2 m, effective size 0.2–0.3 mm) and graded gravel under-drainage. Design rate is 0.1–0.4 m/h; area is determined from Q/rate with one extra unit; cleaning is by scraping the top 1–3 cm when head loss reaches 0.6–1.2 m.

Describe the construction of a slow sand filter with neat sketches and its design consideration.

A slow sand filter (SSF) is a gravity filter in which water passes slowly (0.1 to 0.4 m/h) through a fine sand bed. It works by straining, sedimentation, adsorption and especially biological action, and it needs no chemicals.

Construction

   Inlet          supernatant water 1.0-1.5 m
     |      ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
     v      | schmutzdecke (biological film)
  ______    |:::::::::::::::::::::::::::::|
 |      |   | fine sand 0.9-1.2 m         |
 |      |   |-----------------------------|
 |      |   | gravel 0.3-0.45 m (graded)  |
 |______|   |==under-drain pipes (laterals)|
 Free board 0.5 m       |             |
                   main drain -> clear water
  • Tank: rectangular RCC or masonry, with watertight floor, L : B about 2:1 to 3:1; area up to about 2000 m² per bed, with a minimum of two units.
  • Supernatant water: 1.0 to 1.5 m depth above the sand, plus 0.5 m free board.
  • Filter sand: depth 0.9 to 1.2 m, effective size 0.2 to 0.3 mm, uniformity coefficient 2 to 3 (not more than 5), free of clay and organic matter.
  • Base material: gravel 0.3 to 0.45 m in 3 or 4 layers from 3 mm (top) to 40 mm (bottom).
  • Under-drainage: central main drain with lateral perforated pipes or open-jointed tiles covered with gravel, bed slope 1 in 100.
  • Inlet and outlet chambers with valves, weirs, a filter-to-waste valve, and a rate (flow) controller.

Design considerations

  • Rate of filtration: 0.1 to 0.4 m/h (100 to 400 l/h/m²).
  • Area: A=Q/rateA=Q/\text{rate}, with one extra unit as standby for cleaning.
  • Sand cleaning: when the head loss reaches 0.6 to 1.2 m, remove the top 1 to 3 cm by scraping, and re-sand when the bed depth is below 0.4 to 0.5 m (cleaning every 1 to 3 months).
  • Influent turbidity not above 30 NTU (use a roughing filter or sedimentation for turbid water).
  • After scraping, the filtrate of the first 1 to 2 days is run to waste until the schmutzdecke is formed again.
  • Efficiency: removes 98 to 99 % of bacteria and the turbidity to below 1 NTU; chlorination is still required.