Short answer

Air change per hour (ACH) is the number of times the room air volume is replaced per hour, calculated as ACH = Q/V where Q is airflow rate (m³/h) and V is room volume (m³). Effective temperature (ET) is an index combining dry-bulb temperature, humidity, and air movement into a single value representing the temperature of still, saturated air that would produce the same thermal sensation; comfort zone is 20–27°C ET.

Define the term air change per hour and effective temperature used during study of functional requirement of ventilation.

Air change per hour (ACH)

Air change per hour is the number of times the whole volume of air in a room is replaced by fresh air in one hour.

ACH=QVACH = \frac{Q}{V}

where QQ is the volume of air supplied or removed per hour (m³/h) and VV is the room volume (m³). For example, a 4 m × 5 m × 3 m room with a supply of 360 m³/h has V=60V = 60 m³, so ACH=360/60=6ACH = 360/60 = 6. Typical values: living rooms 3 to 6, kitchens 15 to 30, toilets 6 to 10, assembly halls 8 to 12.

Effective temperature (ET)

Effective temperature is an index that combines dry-bulb temperature, humidity and air movement into one number. It is the temperature of still, saturated air (100 % RH, no air movement) that gives the same feeling of warmth or cold as the actual conditions. It is read from the ET chart (Yaglou and Houghton) using dry-bulb and wet-bulb temperatures and air velocity. The comfort zone is about 20 to 27 °C ET for most people, with the preferred ET at 22 to 25 °C.