- Asked 2/21
- 2078 Chaitra · 14 marks
Braced built-up column, 3 m, 1600 kN
Short answer
Use 2 ISMC 250 back to back with 150 mm clear gap. Provide single lacing with 60×10 mm flats at 45°, M20 bolts, and end tie plates 310×230×6 mm.
Design of braced built-up column using double channel-section, having unsupported length 3.0m, subjected to factored axial load of 1600 kN. Use single lacing as lattice member and bolted connection to connect lacing and column. The ends of the columns are effectively held in position at both ends but not restrained against rotation.
Given/assumptions: factored load kN; unsupported length 3.0 m; ends held in position but not restrained in rotation → , m. Two channels (back to back), single lacing, bolted (M20, grade 4.6); E250 (, ).
1. Section: 2 ISMC 250 back to back (webs facing, flanges outward)
mm², mm⁴, mm, mm, mm. Built-up members use buckling class c (IS 800:2007 Table 10, ).
- Laced column: (cl. 7.6.1.4)
- with , , → N/mm²
- kN kN ✓
2. Clear gap for equal stiffness
The centroid of each section is at from the column axis. For :
Provide mm. Then mm⁴, mm, , , kN ✓.
3. Design of lacing (single lacing, two planes)
|\ /|
| \ / | theta = 45 deg to the axis
| \ / | S = distance between connection lines
| / \ |
| / \ |
- Distance between connection lines mm
- Transverse shear kN; per lacing plane kN
- Force in lacing bar kN
- Length of bar mm; effective length (between the inner end bolts)
- mm → 10 mm; width mm → flat 60 × 10 mm
- ✓ (cl. 7.6.3); N/mm², kN ✓
- Tension: kN ✓
- Connection: M20 (4.6) kN, bearing on 10 mm kN → 1 bolt at each end
- Lacing angle lies between 40° and 70° ✓
- Spacing of lacing points on one section mm; slenderness of the section between them ✓ (cl. 7.6.3)
4. Tie plates
Tie (end) plates at both ends of the lacing system: length edges mm, depth mm, thickness mm → 310 × 230 × 6 mm at each end, connected to each section by 2 bolts.
Answer: 2 ISMC 250 back to back (webs facing, flanges outward), clear gap 150 mm, single lacing of 60 × 10 mm flats at 45°, tie plates 310 × 230 × 6 mm at the ends.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Built-up column with battens, 4 m, 1000 kN · Design of Steel and Timber Structure, chapter 6 · asked 2×
- Built-up column, single lacing, 8 m, 1100 kN · Design of Steel and Timber Structure, chapter 6
- Built-up column, single lacing, 900 kN, 5 m · Design of Steel and Timber Structure, chapter 6
- Built-up column, battens, 6 m unsupported, 1200 kN · Design of Steel and Timber Structure, chapter 6
- Built-up column, lacing, 8 m, 1100 kN · Design of Steel and Timber Structure, chapter 6 · asked 4×
- Built-up laced column, 10 m, 1000 kN · Design of Steel and Timber Structure, chapter 6 · asked 4×
- Built-up column with battens, 10 m, 1080 kN · Design of Steel and Timber Structure, chapter 6 · asked 4×
- Column 400x500, 1600 kN, 4.0 m · Design of RCC Structure, chapter 10
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Short column 400x500, 1600 kN · Design of RCC Structure, chapter 10
- Column design, 1350 kN, 3.4 m · Design of RCC Structure, chapter 10
All Design of Steel and Timber Structure chapter 6 questions →