- 2075 Baisakh · 10 marks
Main beam of 12 m x 12 m floor
Short answer
The end main beam carries three factored point loads 111.94 kN plus self-weight UDL, giving factored moment 704.2 kN·m. Provide ISMB 600 (plastic, laterally restrained); its plastic moment capacity 775.0 kN·m > 704.2 kN·m, shear also safe.
A floor 12 m ×12 m in plan as shown in figure to be covered with a floor made up of secondary and main beams. The secondary beams of 5 KN/m are spaced at 3 m intervals. It supports reinforced concrete slab 125 mm thick and floor finish 0.5 KN/m². If live load on the floor is 3 KN/m², design main beam located at end of floor for bending. Compression flange of main beam is laterally restrained. [Figure: floor plan 12 m x 12 m; main beams at 2 x 6 m spacing; secondary beams at 3 x 4 m spacing, i.e. 3 m c/c]
Data
- Steel Fe 410 (E250): N/mm², N/mm², N/mm², (IS 800:2007, Table 5). Limit state design.
- Effective span m.
Loads and design forces
Arrangement read from the figure (assumption). The floor is 12 m × 12 m. Main beams are 6 m apart (three lines of main beams, each spanning 12 m); secondary beams are at 3 m c/c and span 6 m between main beams. The "5 kN/m" is taken as the self-weight of a secondary beam. The main beam at the end of the floor carries the reaction of one span of each secondary beam, at 3 m, 6 m and 9 m along its 12 m span.
Load on a secondary beam (per metre): slab kN/m², finish , live kN/m², so floor load kN/m². On a 3 m width: kN/m (self-weight) kN/m.
Reaction of a secondary beam on the end main beam kN. Factored point load kN at , and ( m).
Moment without self-weight kN·m, so cm³ (self-weight adds a little).
Trial section
Try ISMB 600 (IS 808): mm, mm, mm, mm, mm; cm⁴; cm³; cm³; mass kg/m.
Self-weight kN/m, factored kN/m. The main beam carries no other distributed load, so the factored UDL is its self-weight, kN/m.
The reaction from the three point loads is . Moment at mid-span ; the self-weight of the main beam is added as a UDL.
Section classification (Table 2)
. Flange: . Web: (with mm). The section is plastic, so .
Moment capacity (cl. 8.2.1.2)
The compression flange of the main beam is laterally restrained (given), so is the plastic moment capacity.
The smaller value governs: kN·m.
Shear capacity (cl. 8.4)
kN ; also kN, so the shear is low and the moment capacity is not reduced (cl. 9.2.1). Web shear buckling does not govern since (cl. 8.4.2.1).
The question asks only for the design for bending; shear is checked above for completeness, and deflection is not checked.
Final design
Provide ISMB 600 (123.0 kg/m): kN·m kN·m, kN kN.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- I-section beam for 9 m x 24 m hall slab · Design of Steel and Timber Structure, chapter 7
- Beam with slab, 20 kN/m, 350 mm wall · Design of Steel and Timber Structure, chapter 7
- RCC floor joist design, 15 m x 6 m hall · Design of Steel and Timber Structure, chapter 7
- Beam supporting RCC slab, DL 10 kN/m, IL 30 kN · Design of Steel and Timber Structure, chapter 7 · asked 2×
- Beam supporting RCC slab, DL 25, IL 20 kN/m · Design of Steel and Timber Structure, chapter 7 · asked 2×
- Beam 6 m span with 100 kN secondary beam load · Design of Steel and Timber Structure, chapter 7
- Cross wall design, 125 mm slab, 3.2 m · Concrete Technology and Masonry Structure, chapter 8 · asked 3×
- Slab panel 2 for BM and SF (floor plan) · Design of RCC Structure, chapter 9
- Slab continuous over three edges, 5x4 m (225 mm beam) · Design of RCC Structure, chapter 9
- Design T-beam with 150 mm slab · Design of RCC Structure, chapter 4
All Design of Steel and Timber Structure chapter 7 questions →