Wind load on industrial truss, 40 m span
Short answer
Using IS 875, Vz = 47 x 1.0 x 1.036 x 1.0 = 48.7 m/s and pz = 0.6Vz^2 = 1.42 kN/m^2. With assumed 20 degree roof slope and Cpi = +/-0.2, the worst net pressure is (Cpe - Cpi) = -0.90, giving 1.28 kN/m^2 suction. Force per truss (5 m spacing) is 272.7 kN; whole roof 5454 kN.
Determine wind load on a roof truss for an industrial building with 40m span and 100m length. The roofing is galvanized iron sheeting. The basic wind speed is 47m/s and terrain is open industrial area and building is class A. The clear height of building at the eaves level is 10m.
Assumptions (data not fully given). m/s (given). Terrain is an open industrial area: Category 2 ("open terrain with scattered obstructions"); Class A (as stated). Life 50 years: ; flat site: . The roof slope is not given, so is assumed (rise m). Eaves height 10 m, so ; mean roof height m. Normal permeability (); GI sheeting. Truss spacing is assumed to be 5 m.
Step 1: Design wind speed (IS 875 Part 3:1987, cl. 5.3)
- Basic wind speed m/s.
- Risk coefficient (50-year life; Table 1).
- Terrain, height and size factor : Category 2, Class A, at height 13.6 m: interpolating between 10 m (1.00) and 15 m (1.05): (Table 2).
- Topography factor (flat site).
Step 2: Pressure coefficients (Table 5, pitched roof of rectangular clad building)
Height ratio , roof angle . The values are read directly from the row, so no interpolation is needed.
Internal pressure coefficient (normal permeability), cl. 6.2.3.
| Surface | () | () | (N/m²), | (N/m²), | |
|---|---|---|---|---|---|
| Windward slope EF (wind 0°) | -0.40 | -0.60 | -0.20 | -854 | -285 |
| Leeward slope GH (wind 0°) | -0.40 | -0.60 | -0.20 | -854 | -285 |
| Slope EG (wind 90°) | -0.70 | -0.90 | -0.50 | -1281 | -712 |
| Slope FH (wind 90°) | -0.60 | -0.80 | -0.40 | -1139 | -569 |
Design pressure normal to the roof: (positive = towards the surface, negative = suction). The most severe case is slope EG (wind 90°), with , so N/m² kN/m².
Step 3: Wind force on the roof / truss
, acting normal to the roof surface. The most severe net coefficient, , is used for the maximum force.
-
One truss (both slopes, slope length 21.28 m each, spacing 5 m): m², kN (suction, i.e. acting away from the roof).
-
Whole roof, 40 m × 100 m plan: m², kN (suction, i.e. acting away from the roof).
Answer
- Design wind speed m/s; design wind pressure N/m² (1.42 kN/m²).
- Net design pressure on the roof: up to N/m² (1.28 kN/m²), suction.
- One truss (both slopes, slope length 21.28 m each, spacing 5 m): 272.7 kN.
- Whole roof, 40 m × 100 m plan: 5454.0 kN.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Wind pressure on roof truss, 20 m span, 30 deg · Design of Steel and Timber Structure, chapter 8
- Max wind force on roof truss, 50 yr, hill crest · Design of Steel and Timber Structure, chapter 8
- Purlin for roof truss, 10 m span · Design of Steel and Timber Structure, chapter 8
- I-section purlin for industrial building · Design of Steel and Timber Structure, chapter 8
- Method of wind load calculation on roof · Design of Steel and Timber Structure, chapter 8 · asked 2×
- Wind pressure on sloping roof, Kathmandu · Design of Steel and Timber Structure, chapter 8
- Good paint characteristics; painting galvanized iron · Engineering Chemistry, chapter 8 · asked 2×
- T-beam decking quantities (6 m clear span) · Estimating and Costing, chapter 6
- Beam with torsion, 4.5 m clear span · Design of RCC Structure, chapter 5
- Couple closed roof and mansard roof truss · Building Technology, chapter 4
All Design of Steel and Timber Structure chapter 8 questions →