Unarmoured cable for 15 hp motor at 79 m
Short answer
Motor full-load current is 23.75 A; design current (125%) is 29.7 A. From the table, 4 mm² unarmoured copper cable rated 31 A is selected. Voltage drop is 11.57 V (2.89%), within 5%. Cable size: 4 mm².
A 3-phase 15 hp, 400V, 50 Hz induction motor is to be installed in a workshop. Assuming the efficiency of the motor to be 85% and power factor 0.8, calculate the size of the unarmoured copper cable to be used if the distance between SDB and motor is 79m.
| Conductor area (sq.mm) | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3.5 core cable current rating (A) | 21 | 27 | 31 | 45 | 60 | 77 | 99 | 120 | 145 | 175 | 210 | 240 | 270 |
Given: P_out = 15 hp, V = 400 V (3-phase), η = 85 %, pf = 0.8, length SDB → motor = 79 m.
Assumptions: 1 hp = 746 W; cable chosen for 125 % of motor full-load current (motor circuit rule of IS 732/NEC); Cu resistivity 0.0178 Ω·mm²/m; permissible voltage drop 5 % (20 V). Table ratings are used for the unarmoured multicore Cu cable.
Step 1: Full-load current
Output P_out = 15 × 746 = 11,190 W
Input P_in = 11190 / 0.85 = 13,164.7 W
I_FL = P_in / (√3 × V × pf)
= 13164.7 / (√3 × 400 × 0.8)
= 23.75 A
Step 2: Design current and cable from table
Design current = 1.25 × 23.75 = 29.69 A
From the table, the next rating above 29.69 A is 31 A → 4 mm².
Step 3: Voltage drop check
R = ρL/A = 0.0178 × 79 / 4 = 0.3515 Ω
ΔV = √3 × I × R × cos φ
= √3 × 23.75 × 0.3515 × 0.8 = 11.57 V
%ΔV = 11.57/400 × 100 = 2.89 % (< 5 %, OK)
Answer: 4 mm² Cu unarmoured (3.5/4-core) cable — full-load current 23.75 A, voltage drop 11.57 V (2.89 %). Protect the motor with a 32 A TP MCB (D-curve) or MPCB and a thermal overload relay set at about 24 A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Cable types and cable for 15 hp motor · Industrial Power Distribution and Illumination, chapter 5 · asked 2×
- Power/light sub-circuits and cable for 50 kW, 60 kW · Industrial Power Distribution and Illumination, chapter 5 · asked 4×
- Workshop hall lighting and power distribution · Industrial Power Distribution and Illumination, chapter 7
- Induction motor improving power factor · Industrial Power Distribution and Illumination, chapter 10
- Cable size MDB to SDB-1 (60 kW) and SDB-2 (75 kW) · Industrial Power Distribution and Illumination, chapter 5 · asked 4×
- Cable size MDB to SDB1 (70 kW) and SDB2 (90 kW) · Industrial Power Distribution and Illumination, chapter 5 · asked 5×
- Rotor copper loss and efficiency of 35 kW induction motor · Electrical Machines I, chapter 5
- 6-pole induction motor: slip, losses, efficiency · Electrical Machines, chapter 5
- One hour rating of a 20 hp induction motor · Electric Machine Design, chapter 2 · asked 2×
- 2.2 kW cage motor designed for best power factor · Electric Machine Design, chapter 4 · asked 2×
All Industrial Power Distribution and Illumination chapter 5 questions →