Flood lighting a 50 × 16 m building
Short answer
Total lumens = 100×800×1.5×1.2/0.5 = 288,000 lm. Assuming 1000 W tungsten-halogen (20 lm/W): 15 projectors. Beam spread ≈ 35°. Alternative: 400 W metal-halide (80 lm/W) yields 9 projectors.
A building elevation is 50m x 16m is to be illuminated by flood lighting projectors situated at 25 meters away. If the illumination is 100 lumen/m², coefficient of utilization is 0.5, depreciation factor 1.5, waste light factor 1.2, estimate the number and size of projectors. Also find out angle of spread.
Given: building face 50 m × 16 m, projectors 25 m away, E = 100 lm/m² (lux), CU = 0.5, depreciation factor DF = 1.5, waste light factor WLF = 1.2.
Total lumens required
Area A = 50 × 16 = 800 m²
Total lm = E × A × DF × WLF / CU
= 100 × 800 × 1.5 × 1.2 / 0.5
= 288 000 lm
Number and size of projectors
Size is not given, so assume 1000 W tungsten-halogen floodlight projectors with efficacy about 20 lm/W (standard textbook assumption):
Lumens per lamp = 1000 × 20 = 20 000 lm
N = 288 000 / 20 000 = 14.4 → 15 projectors
(If 400 W metal-halide lamps of 80 lm/W = 32 000 lm are used instead, N = 9.)
Angle of spread
With projectors 25 m away, aimed at the middle of the face (8 m high), the vertical beam must cover 16 m:
θ = 2 tan⁻¹(8 / 25) = 35.5°
(If projectors are at ground level aimed upward, the face subtends tan⁻¹(16/25) = 32.6°.) So projectors with a medium beam of about 35° are chosen. Horizontally the 15 projectors are spread along the 50 m frontage so that their beams overlap.
Answer: total 288 000 lm; 15 projectors of 1000 W (20 lm/W assumed); beam spread ≈ 35°.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Flood lighting procedure and 50 × 15 m frontage · Industrial Power Distribution and Illumination, chapter 8
- Industry room 30 × 20 m LED lighting and DB · Industrial Power Distribution and Illumination, chapter 7 · asked 2×
- Waste light factor and floodlight calculation · Industrial Power Distribution and Illumination, chapter 8
- Hall 16 × 12 m LED lighting · Industrial Power Distribution and Illumination, chapter 7 · asked 4×
- Industrial shop 30 × 25 m LED lighting · Industrial Power Distribution and Illumination, chapter 7
- Factory hall 55.75 m × 40.25 m LED lighting · Industrial Power Distribution and Illumination, chapter 7 · asked 4×
All Industrial Power Distribution and Illumination chapter 8 questions →