- 2072 Magh · 4 marks
Need for UPS and on-line UPS
Short answer
UPS provides no-break clean power to critical loads during supply disturbances and bridges the gap until the DG starts. On-line UPS always supplies the load from the inverter via rectifier and battery, giving zero transfer time and full isolation; it has lower efficiency and higher cost.
Why UPS is required for industrial electrification? Explain about On-line UPS.
Why UPS is required in industrial electrification
A UPS (Uninterruptible Power Supply) gives continuous, clean AC power to critical loads during supply failure and disturbances.
- PLCs, DCS/SCADA, computers and instruments lose data or trip on even a few milliseconds' interruption.
- It protects equipment from voltage sags, spikes, surges, harmonics and frequency variation.
- It bridges the 10–15 s gap until the DG set starts and takes load.
- It enables safe, orderly shutdown of processes and avoids loss of production.
- It supplies emergency lighting, communication, alarm and security systems.
On-line UPS
In an on-line (double-conversion) UPS, the load is always supplied by the inverter.
- Rectifier/charger converts mains AC to DC, feeds the inverter and keeps the battery charged (float).
- Battery is connected to the DC bus permanently.
- Inverter converts DC to regulated sine-wave AC for the load.
- Static bypass switch transfers the load to mains if the inverter fails or is overloaded.
When mains fails, the battery continues feeding the inverter, so there is zero transfer time.
┌────── static bypass ──────┐
AC ─►[Rectifier]─►DC─►[Inverter]───┴─► Load
│
[Battery]
Advantages: no break, complete isolation from mains disturbances, stable voltage and frequency. Disadvantages: higher cost and losses (efficiency ≈ 90–94%).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Emergency vs back-up supply, online/offline UPS · Industrial Power Distribution and Illumination, chapter 9 · asked 3×
- Importance of emergency supply, online vs offline UPS · Industrial Power Distribution and Illumination, chapter 9
- Industrial shop 30 × 25 m LED lighting · Industrial Power Distribution and Illumination, chapter 7
- Need of energy audit and technique · Industrial Power Distribution and Illumination, chapter 10 · asked 3×
- Maximum demand and need to calculate it · Industrial Power Distribution and Illumination, chapter 1
- Single line diagram from 11 kV to end use · Industrial Power Distribution and Illumination, chapter 4 · asked 3×
- Number of additional rain gauges required · Engineering Hydrology, chapter 2
- Degree of treatment, industrial wastewater · Sanitary Engineering, chapter 6
- Degree of treatment, domestic + industrial · Sanitary Engineering, chapter 6
- Drop manhole: need and construction · Sanitary Engineering, chapter 4 · asked 4×
All Industrial Power Distribution and Illumination chapter 9 questions →