Gas operated Buchholz relay
Short answer
It is mounted in the pipe to the conservator. Slow gas formation from incipient faults lowers the oil level and closes an alarm; a heavy oil surge from severe faults trips the transformer. It is simple, needs no CTs, detects early faults and gas analysis is possible, but only for oil-immersed conservator-type transformers, slow (0.2 s), and cannot protect external faults.
Explain the working of gas operated Buchholz relay used for the protection of a transformer. State its limitations and advantages.
A Buchholz relay is a gas-operated relay mounted in the pipe connecting the main tank of an oil-immersed transformer to the conservator. It protects against all internal faults that produce gas or an oil surge.
Construction
- A domed, oil-filled chamber in the inclined connecting pipe.
- Upper float (hinged) with a mercury switch connected to an alarm circuit.
- Lower float or baffle flap in the path of oil flow, with a mercury switch connected to the trip circuit of the transformer breakers.
- A gas release cock at the top and an inspection window.
gas cock
│
Tank ════════╗ ┌────┴───────┐ ╔════════ Conservator
oil ───────►╠══│ (o)─upper │══╣ (pipe rises gently
║ │ float→A │ ║ towards conservator)
║ │ [flap]─lower│ ║
║ │ float→T │ ║
└────────────┘
A = alarm switch, T = trip switch
Working
- Normal condition: the relay is full of oil; both floats stay up and their contacts are open.
- Incipient faults (core insulation failure, inter-turn short, hot spot, bad joint): heat slowly decomposes the oil; gas bubbles rise to the relay chamber and collect at the top. The oil level falls, and the upper float tilts and closes the alarm circuit.
- Severe faults (earth fault, phase-to-phase winding fault): gas forms rapidly, and the pressure drives a surge of oil through the pipe towards the conservator. This surge tilts the lower float/flap and closes the trip circuit, disconnecting the transformer from both sides.
- Loss of oil (leak): the oil level falls first below the upper float (alarm) and then below the lower float (trip).
- The collected gas is sampled; its colour and analysis show the nature of the fault.
Advantages
- Simplest form of transformer protection; no CTs or external supply needed.
- Detects incipient faults at an early stage, before they become serious, and gives an alarm.
- Detects inter-turn and core faults that differential protection may not see.
- Gas analysis helps to identify the type of fault.
- Also protects against loss of oil.
Limitations
- Usable only for oil-immersed transformers with a conservator.
- Protects only against faults inside the tank; it does not cover bushings, cables or external connections.
- Slow: the minimum operating time is about 0.1 s (average 0.2 s), so differential protection is still needed for fast clearance.
- Can maloperate on oil surges caused by heavy through faults, earthquakes or mechanical shocks, or on air entering after oil filling.
- Economical only for transformers above about 500 kVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Buchholz relay for internal faults · Switchgear and Protection, chapter 7
- Percentage differential relay: 125 MVA transformer · Switchgear and Protection, chapter 7
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- Static differential relay for two-winding transformer · Switchgear and Protection, chapter 8
- Distance protection relay and applications · Switchgear and Protection, chapter 7
- Differential protection of power transformer · Switchgear and Protection, chapter 7
- Working of combined gas-steam plant · Power Plant Equipment, chapter 8
- Protection for alternator and step-up transformer · Power Plant Design, chapter 4
- Transformer protection, selection and vector group · Power Plant Design, chapter 4