Protection for alternator and step-up transformer

Short answer

Essential alternator protections: differential (87G), stator earth fault 95% and 100% (59N/64G, 27TN/64S), rotor earth fault (64R), loss of excitation (40), negative sequence (46). Essential GSU protections: transformer differential (87T), restricted earth fault (64REF), Buchholz (63), overfluxing (24). Overall unit differential (87GT) and master trip (86) cover both.

List out the most essential protection schemes required for Alternator and Generator Step Up transformer in a mega size power project.

In a mega (large) hydro or thermal project, the alternator and its generator step-up (GSU) transformer are protected by a set of main and backup relays, usually grouped as a unit protection scheme with an overall differential zone.

Generator protections (ANSI number)

ProtectionANSIPurpose
Generator differential87GStator phase-to-phase faults
Stator earth fault 95 %59N / 64GEarth faults on 95 % of winding
100 % stator earth fault27TN / 64SFaults near neutral (3rd harmonic or injection)
Rotor earth fault64R / 64FField winding earth fault
Loss of excitation40Field failure, under-excitation
Negative sequence46Unbalanced load, rotor heating
Reverse power32Motoring of the unit
Over/under frequency81Abnormal speed
Over/under voltage59 / 27Load rejection, AVR failure
Overfluxing (V/Hz)24Core over-excitation
Voltage-restrained overcurrent / impedance51V / 21Backup for external faults
Pole slipping78Loss of synchronism
Stator thermal / RTD49Overload, cooling failure
Inadvertent energisation50/27Breaker closed on a stopped unit

GSU transformer protections

ProtectionANSIPurpose
Transformer differential87TInternal phase faults
Restricted earth fault (HV)64REF / 87NEarth faults near HV neutral
Buchholz relay63Incipient internal faults, gas
Oil and winding temperature26 / 49Overheating
Pressure relief device63PRSudden internal pressure
HV overcurrent and earth fault50/51, 50N/51NBackup
Overfluxing24Over-excitation of core
Oil level, cooling failure71Alarm

Overall scheme

An overall (unit) differential 87GT covers the generator, GSU and unit auxiliary transformer together. Relays are duplicated as Main-1 and Main-2 groups with separate CTs and DC supplies for very large units. Trips go through a master trip relay (86) to the GCB, HV breaker, field breaker and turbine shutdown.