Specification for procuring a power transformer

Short answer

Outdoor oil-immersed 3-phase GSU to IEC 60076; e.g. 30 MVA ONAN/37.5 MVA ONAF; 132/11 kV, 50 Hz, YNd11; impedance 10–12.5%; off-circuit tap changer; HV BIL 650 kVp; ONAN/ONAF cooling; guaranteed no-load and load losses; conservator with air cell, Buchholz, PRV, OTI, WTI; routine and type tests.

Develop a typical specification while procuring a power transformer to be used in power plant design.

A technical specification for a power plant's power (step-up) transformer lists the ratings, design, performance and test requirements so that bidders quote a transformer that fits the plant and grid. A typical specification (following IEC 60076) for a hydropower GSU is:

ItemTypical specification
Type, applicationOutdoor, oil-immersed, 3-phase, two-winding, generator step-up
StandardIEC 60076 (all parts)
Rated powere.g. 30 MVA (ONAN) / 37.5 MVA (ONAF)
Rated voltage ratioe.g. 132 / 11 kV
Frequency50 Hz
Vector groupYNd11 (HV star neutral solidly earthed)
ImpedanceAbout 10–12.5% on rated MVA (with tolerance per IEC)
Tap changerOff-circuit ±2 × 2.5% on HV (or OLTC if grid needs it)
CoolingONAN/ONAF (or OFWF in cavern powerhouses)
Insulation level (BIL)HV 650 kVp lightning impulse, 275 kV power frequency (for 145 kV class); LV 75 kVp, 28 kV
Temperature riseTop oil 60 K, average winding 65 K over 40 °C ambient
AltitudeDerating/insulation correction above 1000 m
LossesGuaranteed no-load and load losses, capitalised in bid evaluation
Efficiency, regulationStated at rated load and 0.85 pf
Noise levele.g. below 75 dB(A)
Short-circuit withstand2 s thermal, dynamic per IEC 60076-5
Core and windingCRGO core; copper windings; disc/helical type
OilMineral oil to IEC 60296
BushingsPorcelain/composite, with bushing CTs for protection
AccessoriesConservator with air-cell, silica gel breather, Buchholz relay, PRV, OTI, WTI, MOG, drain/filter valves, rollers, earthing terminals, marshalling box
TestsRoutine (ratio, polarity, resistance, impedance, losses, dielectric), type (temperature rise, impulse) and special tests; FAT witnessed
TransportMax weight and dimensions for hill road access; nitrogen-filled transport if needed
Documents and sparesDrawings, manuals, recommended spares, warranty

The rating is fixed from generator MVA (e.g. two 15 MVA units → 30 MVA), impedance from fault-level and stability studies, and BIL from the insulation coordination of the HV system.