Design: 200 m head plant, bus MVA levels
Short answer
Design discharge Q45% after riparian release is 6.5 m³/s, net head 190 m; output 10.36 MW. Install two 5.3 MW Francis turbines, total 10.6 MW. Use single busbar with bus section breaker.
A typical hydro power plant has the following details:
| Month | Discharge (m³/s) | Flow duration | Discharge (m³/s) |
|---|---|---|---|
| January | 4.62 | Qmax (Q0) | 207.00 m³/s |
| February | 3.80 | Q25% | 18.24 m³/s |
| March | 3.55 | Q45% | 6.82 m³/s |
| April | 4.55 | Q65% | 4.7 m³/s |
| May | 3.22 | Q85% | 3.10 m³/s |
| June | 12.70 | Q95% | 2.17 m³/s |
| July | 32.98 | Qmin | 0.64 m³/s |
| August | 40.26 | ||
| September | 31.23 | ||
| October | 15.00 | ||
| November | 7.37 | ||
| December | 4.80 |
| Turbine type | Head range (m) |
|---|---|
| Kaplan | 2 < H < 40 |
| Francis | 10 < H < 350 |
| Pelton | 50 < H < 1300 |
| Parameter | Value |
|---|---|
| Gross head | 200 m |
| Turbine efficiency | 90% |
| Generator efficiency | 97% |
| Transformer efficiency | 98% |
| Head loss | 5% |
| Riparian release | 10% |
| Generator sub-transient reactance | 21% |
| Transformer reactance | 9.15% |
| Transmission line inductance | 0.95 mH/km |
| Transmission line length | 25 km |
| Transmission voltage level | 33 kV |
| Generator voltage level | 11 kV |
| Transmission circuit | Double circuit |
Design a power plant so as to obtain the following parameters: a) Electrical power output taking design discharge as Q45% b) Select the numbers of units and installed capacity c) Draw the single line diagram showing number of units, generator, power transformer, station transformer and diesel generator for black start d) Select the type of turbine e) Suggest the type of bus bar to be used f) Calculate the MVA level of LV bus, MV bus and HV bus g) Calculate the rating of circuit breaker to be used in your design (Assume suitable data if required and the necessary graph is attached herewith)
Take riparian release as 10% of the driest monthly mean flow, net head = gross head minus 5% loss, and two generating units. The grid's fault contribution is neglected because grid data is not given (only the plant's generators feed a fault).
a) Electrical power output at
Driest month = May (3.22 m³/s), so riparian release m³/s.
Answer: generator output = 10.573 MW; power delivered to the 33 kV bus = 10.362 MW.
b) Number of units and installed capacity
- Choose 2 units. The plant runs on , so in the dry season (flow below about ) one unit can still run near its best efficiency; one unit can be maintained while the other runs; and two units keep the number of machines (and cost) low for a plant of this size.
- Per unit: m³/s, generator output MW.
- Generator rating: 5.3 MW at 0.85 pf, i.e. MVA → 6.25 MVA, 11 kV, 50 Hz.
- Step-up transformer: one per unit, 6.3 MVA, 11/33 kV, YNd11, 9.15% (next standard size above 6.25 MVA).
Answer: installed capacity = 2 × 5.3 MW = 10.6 MW.
c) Single line diagram
Line-1 33 kV Line-2 33 kV
(25 km) (25 km)
| |
[CB] [CB]
| |
33 kV ==+=======[BS]========+==
| |
[CB] [CB]
| |
(T1) (T2)
11/33 kV 6.3 MVA 11/33 kV 6.3 MVA
| |
[CB] [CB]
| |
11 kV ==+=====[BS]======+===+===+==
| | |
[GCB] [GCB] [CB]
| | |
(G1) (G2) (ST) 11/0.4 kV
6.25 MVA 6.25 MVA 250 kVA
|
0.4 kV aux bus ===+===+==
|
[ACB]
|
(DG) 200 kVA
BS = bus section breaker; ST = station (auxiliary) transformer; DG = diesel generator for black start. With the grid dead, the DG energises the 0.4 kV auxiliary bus (governor oil pumps, cooling water, excitation field flashing, lighting, battery chargers), so a unit can be started without outside supply.
d) Selection of turbine
m lies in both the Francis (10–350 m) and Pelton (50–1300 m) ranges, so specific speed decides. Per-unit shaft power kW; take rpm (6-pole, 50 Hz synchronous speed).
A single-jet Pelton suits – (up to about 60–70 with multiple jets); a Francis suits –. falls in the slow-to-medium Francis range, and a Francis has good efficiency at this discharge per unit (about 3.249 m³/s).
Answer: 2 × vertical-axis Francis turbines, 1000 rpm.
e) Type of bus bar
- 11 kV: single bus bar with a bus-section breaker. Each half carries one unit, so a bus fault or maintenance takes out only one unit.
- 33 kV switchyard: single bus bar, sectionalised, with one bay for each circuit of the double-circuit line. This is simple and cheap for a 10.6 MW, 2-unit plant. A double bus or main-and-transfer bus costs more and is normally used only in larger plants or grid nodes.
f) MVA (fault) level of the LV, MV and HV buses
Take LV = 0.4 kV auxiliary bus, MV = 11 kV generator bus, HV = 33 kV switchyard bus. Base = 10 MVA. Station transformer assumed 250 kVA, 4.5%.
| Fault location | Equivalent (pu) | Fault MVA | (kA) |
|---|---|---|---|
| MV bus (11 kV) | 59.5 | 3.12 | |
| HV bus (33 kV) | 41.6 | 0.727 | |
| LV bus (0.4 kV) | 5.08 | 7.33 |
Line check (remote end): per circuit, 3.731 Ω for both circuits in parallel. , so pu. Fault level at the far end of the line is MVA (0.636 kA).
Answer: LV ≈ 5.08 MVA, MV ≈ 59.5 MVA, HV ≈ 41.6 MVA.
g) Rating of circuit breakers
Making current = (peak, IEC 62271-100). Rated current ≥ 1.25 × full-load current.
| Item | Generator CB (11 kV) | HV line/transformer CB (33 kV) |
|---|---|---|
| Full-load current | A | 110 A per transformer, 220 A total |
| Required breaking | 3.12 kA (59.5 MVA) | 0.727 kA (41.6 MVA) |
| Required making | 7.97 kA peak | 1.85 kA peak |
| Selected rating | 12 kV, 630 A, 25 kA, VCB | 36 kV, 630 A, 25 kA, SF6 |
Answer: GCB: 12 kV, 630 A, breaking capacity ≥ 59.5 MVA (3.12 kA); 33 kV CB: 36 kV, 630 A, breaking capacity ≥ 41.6 MVA (0.727 kA). Standard 25 kA breakers are chosen because they cost little more and leave margin for the grid's fault contribution and future units.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Design: 230 m head plant, 20 km line · Power Plant Design, chapter 4 · asked 14×
- Design: 250 m head plant at Q25% · Power Plant Design, chapter 4 · asked 14×
- Design: 250 m head plant, 66 kV double circuit · Power Plant Design, chapter 4 · asked 13×
- Design: 250 m head plant, 35 km line · Power Plant Design, chapter 4 · asked 12×
- Design: 230 m head plant, 45 km line · Power Plant Design, chapter 4 · asked 12×
- Design: 245 m head plant, standby generator · Power Plant Design, chapter 4 · asked 14×
- Design: 95 m head plant at Q65% · Power Plant Design, chapter 4 · asked 12×
- Design: 280 m head plant, 66 kV · Power Plant Design, chapter 4 · asked 12×
- Design: 230 m head plant, 55 km line · Power Plant Design, chapter 4 · asked 12×
- Design: 330 m head plant, 132 kV · Power Plant Design, chapter 4 · asked 12×
- Design: 120 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Design: 150 m head plant, bus MVA levels · Power Plant Design, chapter 4 · asked 8×
- Design: 300 m head plant, GCB rating · Power Plant Design, chapter 4 · asked 11×
- Design: 360 m head plant, 132 kV · Power Plant Design, chapter 4 · asked 5×
- Design: 260 m head plant, generator lead · Power Plant Design, chapter 4 · asked 5×
- Load duration curve; diesel plant; ROR flow duration · Hydropower Engineering, chapter 3
- Micro hydro net head, power and energy · Energy Resources, chapter 5
- Flow duration curve and power at mean flow · Hydropower Engineering, chapter 3
- Bus reactor between 100 MVA and 200 MVA generators · Power Plant Equipment, chapter 4