Design: 95 m head plant at Q65%

Short answer

Electrical output 2.73 MW; installed 2.8 MW (2×1.4 MW Francis, 1000 rpm). Single bus at 11 kV and 66 kV. Generator breaker: 11 kV, 630 A, 40 kA; HV breaker: 66 kV, 630 A, 20 kA.

A typical hydropower plant has the following details:

MonthDischarge (m³/s)Flow durationDischarge (m³/s)
January3.30Qmax (Q0)110.00 m³/s
February2.20Q25%16.42 m³/s
March1.40Q45%6.82 m³/s
April1.00Q65%3.7 m³/s
May3.50Q85%2.10 m³/s
June6.00Q95%1.17 m³/s
July14.00Qmin0.64 m³/s
August35.00
September24.00
October12.00
November7.50
December5.00
Turbine typeHead range (m)
Kaplan2 < H < 40
Francis10 < H < 350
Pelton50 < H < 1300
ParameterValue
Gross head95 m
Turbine efficiency90%
Generator efficiency97%
Transformer efficiency98%
Head loss5%
Riparian release10%
Generator sub-transient reactance20%
Transformer reactance11%
Transmission line inductance0.77 mH/km
Transmission line length80 km
Transmission voltage level66 kV
Generator voltage level11 kV
Transmission circuitSingle circuit

Design a hydro power plant so as to obtain following parameters a) Electrical power output taking design discharge as Q65%. [1] b) Select the numbers of unit and installed capacity. [2] c) Select the type of turbine. [3] d) Select the type of bus bar to be used. [2] e) Draw the single line diagram showing number of units, generator, power transformer, station transformer and diesel generator for black start. [4] f) Calculate the rating of generator circuit breaker and high voltage circuit breaker in your design. [4]

Assumptions: riparian release = 10% of the driest monthly mean flow; net head = gross head minus 5% loss; ρg=9.81\rho g = 9.81 kN/m³; generator power factor 0.85; base = 100 MVA. For fault levels the grid is taken as a source of 1,000 MVA at the 66 kV grid substation at the far end of the line (an assumed typical value, since grid data is not given).

a) Electrical power output at Q65%Q_{65\%}

Driest month = April (1 m³/s), so riparian release Qr=0.1×1=0.1Q_r = 0.1 \times 1 = 0.1 m³/s.

Qd=Q65%−Qr=3.7−0.1=3.600 m3/sHn=Hg(1−0.05)=95−4.75=90.25 mPhyd=ρgQdHn=9.81×3.600×90.25=3.187 MWPshaft=ηtPhyd=0.9×3.187=2.869 MWPgen=ηgPshaft=0.97×2.869=2.782 MWPout=ηtrPgen=0.98×2.782=2.727 MW\begin{aligned} Q_d &= Q_{65\%} - Q_r = 3.7 - 0.1 = 3.600\ \text{m}^3/\text{s} \\ H_n &= H_g(1 - 0.05) = 95 - 4.75 = 90.25\ \text{m} \\ P_{hyd} &= \rho g Q_d H_n = 9.81 \times 3.600 \times 90.25 = 3.187\ \text{MW} \\ P_{shaft} &= \eta_t P_{hyd} = 0.9 \times 3.187 = 2.869\ \text{MW} \\ P_{gen} &= \eta_g P_{shaft} = 0.97 \times 2.869 = 2.782\ \text{MW} \\ P_{out} &= \eta_{tr} P_{gen} = 0.98 \times 2.782 = 2.727\ \text{MW} \end{aligned}

Answer: generator output = 2.782 MW; power delivered to the 66 kV bus = 2.727 MW.

b) Number of units and installed capacity

  • Choose 2 units. With a run-of-river flow that falls well below the design flow in the dry months, one unit can run near full load on half the design flow, so efficiency stays high in winter.
  • One unit can be maintained while the other runs, and two units keep the number of machines (and cost) low for a plant of this size.
  • Per unit: Q=3.600/2=1.800Q = 3.600/2 = 1.800 m³/s, generator output =2.782/2=1.391= 2.782/2 = 1.391 MW → rate each unit at 1.4 MW.
  • Generator rating: S=1.4/0.85=1.65S = 1.4/0.85 = 1.65 MVA → 2 MVA, 11 kV, 0.85 pf, 50 Hz.
  • One step-up transformer for both units: 4 MVA, 11/66 kV, YNd11 (standard size covering 2 × 1.65 MVA = 3.3 MVA).

Answer: installed capacity = 2 × 1.4 MW = 2.8 MW.

c) Type of turbine

Hn=90.25H_n = 90.25 m lies in the Francis (10–350 m) and Pelton (50–1300 m) ranges, so the specific speed decides.

Shaft power per unit P=2.869/2=1434.3P = 2.869/2 = 1434.3 kW. With N=120f/pN = 120f/p (synchronous speeds) and Ns=NP/Hn5/4N_s = N\sqrt{P}/H_n^{5/4}, where Hn5/4=278.2H_n^{5/4} = 278.2:

NN (rpm)PolesNsN_s (metric, kW)
10006136.1
7508102.1
6001081.7
5001268.1
428.61458.4
3751651.1
333.31845.4

Usual ranges: Pelton about 10–30 per jet (multi-jet Ns=Ns,jetzN_s = N_{s,jet}\sqrt{z}), Francis about 60–300, Kaplan 300–1000.

Choose N=1000N = 1000 rpm (6 poles): Ns=136.1N_s = 136.1, which is in the medium Francis range. A Pelton would need many jets (single-jet NsN_s far above 30), and Kaplan is ruled out because the head is above 40 m.

Answer: 2 × vertical-axis Francis turbines, 1000 rpm, about 1.43 MW each.

d) Type of bus bar

  • 11 kV: single bus bar; the two small generators and the transformer feeder are connected to it through VCB panels.
  • 66 kV: single bus bar with one transformer bay and one line bay.

Reason: the plant is only 2.8 MW with one line, so a simple single bus is the most economical; an outage of the bus means loss of a small block of power only, and maintenance can be planned for the dry season.

e) Single line diagram

 Line to grid  (66 kV, 80 km)
    |
  [CB]
    |
 ===+======+=== 66 kV bus
           |
         [CB]
           |
         (T1)
           |
         [CB]
           |
 ===+======+======+=========+=== 11 kV bus
    |             |         |
  [GCB]         [GCB]     [CB]
    |             |         |
  (G1)          (G2)      (ST)
                            |
 ===========================+===+ 0.4 kV
                                |
                              [ACB]
                                |
                              (DG) black start
ItemRating
Generators G1–G22 MVA, 11 kV, 0.85 pf, 1000 rpm, Xd′′X''_d = 20%
Step-up transformer T14 MVA, 11/66 kV, YNd11, XX = 11%
Station transformer ST100 kVA, 11/0.4 kV, Dyn11, 4.5% (aux load about 1.5% of capacity)
Diesel generator DG62.5 kVA, 0.4 kV (essential auxiliaries for black start)
Line66 kV, single circuit, 80 km to grid substation
NGRneutral grounding resistor (low-resistance earthing, one generator earthed at a time if preferred)

GCB = generator circuit breaker, ACB = air circuit breaker. Black start: with the grid dead, the DG energises the 0.4 kV auxiliary bus (governor oil pumps, cooling water, excitation field flashing, lighting and battery chargers), one unit is started and runs in island mode, and it then energises the step-up transformer and the line.

f) Rating of generator circuit breaker (GCB)

Per-unit reactances on 100 MVA base:

xg=0.2×1002=10.0000 pu,xt=0.11×1004=2.7500 puXL=2πfLl=2π×50×0.77×10−3×80=19.352 Ωxl=XL×100662=19.35243.56=0.4443 pu,xgrid=1001000=0.1000 puxgrid path=0.1000+0.4443=0.5443 pu\begin{aligned} x_g &= 0.2 \times \frac{100}{2} = 10.0000\ \text{pu}, \quad x_t = 0.11 \times \frac{100}{4} = 2.7500\ \text{pu} \\ X_L &= 2\pi f L l = 2\pi \times 50 \times 0.77\times10^{-3} \times 80 = 19.352\ \Omega \\ x_l &= \frac{X_L \times 100}{66^2} = \frac{19.352}{43.56} = 0.4443\ \text{pu}, \quad x_{grid} = \frac{100}{1000} = 0.1000\ \text{pu} \\ x_{grid\ path} &= 0.1000 + 0.4443 = 0.5443\ \text{pu} \end{aligned}

All generators feed the common 11 kV bus, so the GCB is rated for the full 11 kV bus fault level (generators plus the grid through the step-up transformers):

Sgen=2×10010.0000=20.0 MVASgrid=100xt+xgrid path=1002.7500+0.5443=30.4 MVAS11kV=20.0+30.4=50.4 MVA\begin{aligned} S_{gen} &= 2 \times \frac{100}{10.0000} = 20.0\ \text{MVA} \\ S_{grid} &= \frac{100}{x_t + x_{grid\ path}} = \frac{100}{2.7500 + 0.5443} = 30.4\ \text{MVA} \\ S_{11kV} &= 20.0 + 30.4 = 50.4\ \text{MVA} \end{aligned} Isc=50.43×11=2.64 kA,Imake=2.55×2.64=6.74 kA peakIFL=23×11=105 A,1.25IFL=131 A\begin{aligned} I_{sc} &= \frac{50.4}{\sqrt{3} \times 11} = 2.64\ \text{kA}, \quad I_{make} = 2.55 \times 2.64 = 6.74\ \text{kA peak} \\ I_{FL} &= \frac{2}{\sqrt{3} \times 11} = 105\ \text{A}, \quad 1.25 I_{FL} = 131\ \text{A} \end{aligned}
ParameterRequiredSelected
Rated voltage11 kV system12 kV
Rated normal current≥ 131 A630 A
Breaking capacity50.4 MVA (2.64 kA)25 kA (520 MVA at 12 kV)
Making capacity6.74 kA peak63 kA peak
Short-time current–25 kA, 3 s
Type–Vacuum (or SF6), generator-duty tested (IEEE C37.013)

Answer: GCB fault level = 50.4 MVA; select a 12 kV, 630 A, 25 kA generator circuit breaker. The margin covers the DC component and delayed current zeros of generator faults; surge arresters and surge capacitors are fitted at the generator terminals when a VCB is used.

f) (contd.) Rating of HV circuit breaker

For a fault on the 66 kV bus, the plant and the grid feed in parallel:

Xplant=xg2+xt1=5.0000+2.7500=7.7500 puSHV=1007.7500+1000.5443=12.9+183.7=196.6 MVAIsc=196.63×66=1.72 kA,Imake=2.55×1.72=4.39 kA peakIFL=1×43×66=35 A\begin{aligned} X_{plant} &= \frac{x_g}{2} + \frac{x_t}{1} = 5.0000 + 2.7500 = 7.7500\ \text{pu} \\ S_{HV} &= \frac{100}{7.7500} + \frac{100}{0.5443} = 12.9 + 183.7 = 196.6\ \text{MVA} \\ I_{sc} &= \frac{196.6}{\sqrt{3} \times 66} = 1.72\ \text{kA}, \quad I_{make} = 2.55 \times 1.72 = 4.39\ \text{kA peak} \\ I_{FL} &= \frac{1 \times 4}{\sqrt{3} \times 66} = 35\ \text{A} \end{aligned}
ParameterRequiredSelected
Rated voltage66 kV system72.5 kV
Rated normal current≥ 44 A630 A
Breaking capacity196.6 MVA (1.72 kA)25 kA
Making capacity4.39 kA peak63 kA peak
BIL–325 kVp
Type–SF6, outdoor, spring mechanism, 3-pole

Answer: HV bus fault level = 196.6 MVA (1.72 kA); select a 72.5 kV, 630 A, 25 kA SF6 circuit breaker. Of this, the plant itself contributes only 12.9 MVA; the rest comes from the grid, so the result depends on the assumed grid fault level.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power Plant Design chapter 4 questions →