Short answer

Core electrical protections: differential (87G), stator earth fault (64G), rotor earth fault (64R), loss of excitation (40), negative sequence (46), reverse power (32), voltage-restrained overcurrent (51V) or impedance (21), thermal overload (49), over/under voltage/frequency, overfluxing (24), out-of-step (78). Mechanical: overspeed, bearing/vibration.

List out the necessary protection schemes to be employed for a medium size generator in a power plant.

A medium size generator (roughly 5–100 MVA) is protected against internal faults, abnormal operating conditions and system disturbances. Typical schemes, with ANSI device numbers:

ANSIProtectionPurpose
87GGenerator differentialFast clearing of stator phase-to-phase faults
87GT / 87TOverall gen-transformer / transformer differentialFaults in GSU and connections
64G (59N + 27TN)Stator earth fault (95% neutral overvoltage + 100% third harmonic)Earth faults in stator winding (high-resistance grounded via NGT)
64RRotor (field) earth faultFirst earth fault in field winding
40Loss of excitation (field failure)Prevents running as induction generator and drawing VArs
46Negative phase sequenceUnbalanced loads/open phase; rotor heating
32Reverse powerMotoring when turbine power is lost
51V / 21Voltage-restrained overcurrent / impedanceBackup for external faults
49Stator thermal overload (RTDs)Overheating
59 / 27Over/under voltageLoad rejection, AVR failure
81O / 81UOver/under frequencySpeed and grid frequency deviations
24Overfluxing (V/Hz)Protects generator and GSU core
78Pole slipping (out of step)Loss of synchronism
50/27Inadvertent energisationBreaker closed at standstill
50BFBreaker failureBackup tripping of adjacent breakers

Mechanical/hydraulic protections

Overspeed, bearing and oil temperature, vibration, cooling water failure, low oil pressure, shear pin failure.

Tripping logic

Faults like 87G, 64G, 64R (second stage) trip the GCB, field breaker and turbine (emergency shutdown); abnormal conditions like 46, 49 or 81 first alarm, then trip after a time delay.