- 2070 Bhadra · 8 marks
Static differential relay for two-winding transformer
Short answer
A static differential relay for a two-winding transformer compares HV and LV CT currents after interposing CTs correct ratio and 30° phase shift. The bias circuit produces a restraint voltage proportional to through current; the spill circuit produces an operating voltage from the differential current. A 2nd-harmonic filter provides restraint during magnetizing inrush. An amplitude comparator checks if operating voltage exceeds K×restraint plus harmonic voltage; a high-set unit trips instantly for heavy internal faults. Output trips both HV and LV breakers.
Describe the circuit of static differential relay for protection of two winding transformer.
For a two-winding power transformer, a static differential relay compares the currents of the HV and LV CTs (after ratio and phase correction) and trips when the spill current exceeds a set percentage of the through current, with harmonic restraint to stay stable during magnetising inrush.
Circuit / block diagram (one phase)
HV══CT1════[TRANSFORMER]════CT2══LV
│ (Δ/Y) │
[Interposing CT, [Interposing CT,
ratio & 30° corr.] ratio & 30° corr.]
│ i1 i2 │
├──[Bias rect.]──┬─[Bias rect.]──┤
│ │ V_r │
└──────[Spill CT / summing]──────┘
│ i1 − i2
┌───────────┼─────────────┐
[Fundamental] [2nd harmonic] [Unrestrained
filter → filter → high-set
rectifier] rectifier] level det.]
│ V_o │ V_h │
┌─────▼─────────────▼──┐ │
│ Comparator: │ │
│ V_o > K·V_r + V_h ? │ │
└─────────┬────────────┘ │
└──────────[OR]──────────┘
│
[Amplifier → thyristor]
│
Trip HV & LV CBs
Description of the circuit
- Main CTs and interposing CTs: main CTs on both sides; interposing (auxiliary) CTs match the current magnitudes (inverse of voltage ratio) and correct the 30° phase shift of Δ/Y connection. They also remove zero-sequence currents so that external earth faults do not cause tripping.
- Bias (restraint) circuit: i1 and i2 are rectified separately and summed across resistors to give V_r ∝ (|i1| + |i2|)/2 – the through current.
- Operating (spill) circuit: the difference current (i1 − i2) is passed through a filter tuned to 50 Hz and rectified to give V_o.
- Second-harmonic restraint: a 100 Hz filter extracts the 2nd harmonic in the spill current. During inrush (2nd harmonic > about 15–20% of fundamental) V_h becomes large and blocks tripping. A 5th-harmonic filter may be used for over-excitation restraint.
- Comparator: an amplitude comparator (op-amp) checks V_o > K·V_r + V_h. K is the bias slope (15–40%) which covers CT mismatch, tap-changer range and CT errors.
- Unrestrained (high-set) unit: for very heavy internal faults (spill > 8–10 × rating) it trips immediately without waiting for harmonic analysis, because CT saturation may produce harmonics.
- Output: OR gate, amplifier and thyristor/auxiliary relay trip both HV and LV circuit breakers.
Result: stable for load, external faults and inrush; fast (about 1–2 cycles) and sensitive for internal winding faults.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Static differential relay · Switchgear and Protection, chapter 8 · asked 3×
- Percentage differential relay: 125 MVA transformer · Switchgear and Protection, chapter 7
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- Differential protection of power transformer · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Percentage bias in differential relay · Switchgear and Protection, chapter 7
- Reluctances and air gap flux of two-winding core · Electrical Machines I, chapter 1
- Protection for alternator and step-up transformer · Power Plant Design, chapter 4
- Transformer protection, selection and vector group · Power Plant Design, chapter 4
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×