CT working principle and applications

Short answer

A current transformer (CT) is an instrument transformer with primary in series with the line, delivering a reduced secondary current (1A or 5A) to meters and relays. It operates on electromagnetic induction with secondary nearly short-circuited; primary ampere-turns are balanced by secondary ampere-turns, leaving only small exciting current. Applications include metering (ammeters, energy meters), protection (overcurrent, differential, distance relays), core-balance earth-fault detection, SCADA, and isolation from high voltage.

Define current transformer, its working principle and their application areas.

A current transformer (CT) is an instrument transformer whose primary winding carries the line current in series with the circuit and whose secondary delivers a proportionally reduced current (1 A or 5 A) to meters and relays, with a known phase relation.

Working principle

It works on the principle of electromagnetic induction, like a transformer operating with its secondary nearly short-circuited.

     I_p (line current)
  ═══════════╦═══════════  1 or few turns
          ┌──╨──┐
          │core │  flux Φ
          └──╥──┘
        N_s turns
        ┌────╨────┐
        │  A / R  │ ammeter/relay
        └─────────┘ low impedance burden
  • The primary current is fixed by the load of the line, not by the CT.
  • It sets up primary ampere-turns N_p·I_p. The secondary current I_s produces opposing ampere-turns; only a small difference remains to magnetise the core:
 N_p·I_p ≈ N_s·I_s   →   I_s ≈ I_p × (N_p/N_s)
  • Example: a 500/5 A CT gives 5 A at 500 A primary; turns ratio 1:100.
  • The flux density is low in normal operation; if the secondary is opened, the full primary ampere-turns magnetise the core, causing saturation and dangerously high secondary voltage. Hence the secondary must never be open-circuited.

Types

Wound type, bar type, window/ring type, bushing type, core-balance CT.

Application areas

  1. Metering: ammeters, wattmeters, energy meters, power-factor meters on HV/LV feeders and tariff metering.
  2. Protection: overcurrent and earth-fault relays, differential protection of transformers, generators and busbars, distance and directional relays.
  3. Core-balance CTs: earth-leakage and sensitive earth-fault protection of cables and motors.
  4. Control and monitoring: SCADA transducers, maximum demand indicators, power quality meters.
  5. Isolation: keeps meters and personnel away from high voltage.