Zones of protection and their rules
Short answer
A zone of protection is the region guarded by a protection scheme, bounded by CTs. Adjacent zones overlap across circuit breakers to avoid blind spots. Rules: every element must lie in at least one zone, the overlap contains a breaker with CTs on opposite sides, and a fault in the overlap trips both zones.
What do you understand by a zone of protection? Draw the protection zone diagram for a sample (modern) power system network and explain its rules.
A zone of protection is the part of the power system (generator, transformer, bus, line or motor) protected by a particular protection scheme. A fault anywhere inside the zone makes all the circuit breakers on its boundary trip, so that the zone is fully isolated. The boundary of a zone is defined by the location of the CTs and the circuit breakers.
Protection zones of a sample power system
┌──────────────┐
│ G Gen │ 1 Generator zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ Gen-transf. │ 2 Transformer zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ HV bus │ 3 Bus zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ Line │ 4 Transmission line zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ Rx bus │ 3 Bus zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ Step-down Tr│ 2 Transformer zone
└──┬───────────┘
┌──┴─[CB]──────┐
│ Feeders/Mtr │ 5 Feeder / motor zone
└──────────────┘
Each box is a zone; adjacent boxes
overlap around the circuit breaker.
Rules for drawing zones
- Each zone is drawn around one main element: generator, transformer, bus, line or motor.
- Every element of the system must lie in at least one zone; there should be no blind (unprotected) spot.
- Adjacent zones overlap, and the overlap region contains a circuit breaker. This is done by placing the CTs of the two zones on opposite sides of the breaker.
- A fault inside the overlap region trips the breakers of both zones; the overlap is kept as small as possible so that only a small extra part is disconnected.
- Zone boundaries are set by CT location; a zone includes the breakers that must trip to isolate it.
Using zones makes the scheme selective: a fault on the line trips only the two line breakers, while generator, transformers and buses stay in service.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Requirements, coordination and protection zone · Switchgear and Protection, chapter 1
- Differential protection of power transformer · Switchgear and Protection, chapter 7
- Protection requirements; protective system vs scheme · Switchgear and Protection, chapter 1
- Zones and backup for breaker 7 failure · Switchgear and Protection, chapter 1
- Ring bus rearrangement and zones · Switchgear and Protection, chapter 1
- Overlapping zones and qualities of relaying · Switchgear and Protection, chapter 1
- Typical power system network and components · Power System Analysis I, chapter 1
- Power electronics in modern power systems · High Voltage Engineering, chapter 1
- LTI system and closed loop in modern systems · Control Systems, chapter 1
- Three phase system and transition zone · Concrete Technology and Masonry Structure, chapter 2 · asked 8×