Reactors in stations: merits and demerits

Short answer

Generator reactors limit generator fault current but cause constant drop and loss. Feeder reactors protect individual feeders and keep bus voltage up, but not bus faults, and cause feeder loss. Bus-bar reactors (ring or tie-bar) have low normal loss and confine faults to sections; tie-bar adds extra bus and unbalanced-section voltage differences. Generator reactors are rarely used, feeder reactors suit distribution substations, bus-bar reactors suit large stations.

Explain reactors used in generating stations and substations with diagram. Also discuss their merits and demerits along with field of application.

A reactor is an inductive coil with high reactance and negligible resistance. In generating stations and substations it is used to limit short-circuit current, localise faults, and keep bus voltage up on healthy sections. Air-core (dry, concrete-supported) reactors are common because their reactance does not fall by saturation at high fault current.

1. Generator reactors

  G1      G2      G3
  |       |       |
 [X]     [X]     [X]
  |       |       |
 =+=======+=======+===  bus
     |       |
  feeders
  • Merits: protects each generator from heavy fault current; useful for old machines with low reactance.
  • Demerits: always carries full load current, so constant voltage drop and I2RI^2R loss; a bus or feeder fault still affects all generators; gives no protection between feeders.
  • Application: rarely used now, since modern generators have enough leakage reactance.

2. Feeder reactors

  G1      G2
  |       |
 =+===+===+===+===  bus
      |       |
     [X]     [X]
      |       |
   feeder1  feeder2
  • Merits: a fault on one feeder hardly affects bus voltage, so other feeders keep supplying; breaker ratings of feeders reduced.
  • Demerits: no protection for bus-bar faults; constant drop and loss on every feeder; poor regulation.
  • Application: distribution substations with many radial feeders.

3. Bus-bar reactors

(a) Ring system

  G1          G2          G3
  |           |           |
 =S1===[X]===S2===[X]===S3=
  |                        |
  +----------[X]-----------+

(b) Tie-bar system

  G1      G2      G3
  |       |       |
 =S1=    =S2=    =S3=   sections
  |       |       |
 [X]     [X]     [X]
  |       |       |
 =+=======+=======+=  tie-bar
  • Merits: in normal operation little current flows through bus reactors, so loss and drop are small; a fault is confined to one section; tie-bar system lets sections be added easily, and fault current from other sections passes through two reactors in series.
  • Demerits: a fault on a section gets full fault current from its own generator; tie-bar needs an extra bus; large voltage difference between sections if loads are unbalanced.
  • Application: large generating stations with several sections and many generators.

Summary

SchemeNormal lossMain protection
Generator reactorHighLimits each generator's fault current
Feeder reactorHighLimits feeder-fault current; keeps bus voltage up
Bus-bar (ring/tie-bar)LowConfines a fault to one section