Effect of load rejection
Short answer
Load rejection removes the load current, so the voltage drop across generator and transformer reactances disappears, causing a temporary power-frequency overvoltage. Ferranti effect raises the receiving-end voltage on a long open line, and generator overspeed and possible self-excitation add to it. This sustained overvoltage sets surge-arrester rating.
Explain in brief the effect of load rejection in power system.
Load rejection is the sudden loss of a large load, for example when a breaker at the receiving end trips while the generator stays connected to the line. It causes a temporary overvoltage that can last from several cycles up to seconds.
Effects
- Loss of voltage drop. Before rejection, the load current caused a drop across the generator and transformer reactances. When it vanishes, the terminal voltage jumps towards the internal emf , which may be 1.1–1.2 pu.
- Ferranti effect. The line is suddenly at no load. Its charging current raises the receiving-end voltage by the factor , which is significant on long EHV lines.
- Generator overspeed. The prime-mover input cannot be cut instantly, so the machine accelerates. Voltage rises in proportion to speed (and frequency), until the governor acts.
- Self-excitation. A generator feeding a long open line sees a capacitive load. Its armature current then aids the field flux, and the voltage can build up uncontrolled if the line charging exceeds the machine's capability.
- The overvoltage is at power frequency and lasts long. Surge arresters cannot absorb it for long, so it sets the arrester rating and the insulation design for temporary overvoltage.
Gen --[X']--+------- long line -------x CB trips
| (load lost)
V rises: E' + Ferranti + overspeed
Remedies
- Shunt reactors at the line ends.
- Fast-acting AVR and governor; SVC or STATCOM.
- Generator transformer and line protection that trips the line or generator if the voltage stays high.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- True/false: load rejection raises terminal voltage · High Voltage Engineering, chapter 3
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- FACTS devices changing the power system · High Voltage Engineering, chapter 1
- Vision of power system 25 years ahead · High Voltage Engineering, chapter 1
- Issues of EHV-AC power transmission · High Voltage Engineering, chapter 1
- Accurate load forecasting and system security · Power Plant Design, chapter 2
- Pile capacity in sand, group effect, load test · Foundation Engineering, chapter 8
- Armature reaction at different load power factors · Electric Machines II, chapter 1 · asked 7×
- Bunching, field effect and high power oscillator · RF and Microwave Engineering, chapter 5