Armature reaction at different load power factors
Short answer
Armature reaction is the effect of stator current on the rotor field flux. At unity pf it is cross-magnetizing (slight voltage drop), at lagging pf demagnetizing (large drop, V<E), and at leading pf magnetizing (voltage rise, V>E). It is represented by reactance Xa in the equivalent circuit.
What is meant by armature reaction in a synchronous generator? Explain the effect of armature reaction on the terminal voltage (emf) of an alternator at (i) unity power factor (resistive) load, (ii) lagging power factor (inductive) load and (iii) leading power factor (capacitive) load. Draw relevant phasor diagrams.
Armature reaction is the effect of the magnetic field set up by the armature (stator) current on the main field flux produced by the rotor poles. When the alternator is loaded, the three-phase armature currents produce a rotating mmf that rotates at synchronous speed along with the rotor. This mmf distorts, weakens or strengthens the main flux depending on the power factor of the load, and so changes the terminal voltage.
In the equivalent circuit, armature reaction is represented by a fictitious reactance ; together with the leakage reactance it forms the synchronous reactance , and
(i) Unity power factor (resistive) load
- The armature current is in phase with the emf, so each conductor carries its maximum current at the instant it is under the centre of a pole (where its emf is maximum). The armature mmf is then at 90° (in quadrature) to the main flux.
- The effect is cross-magnetising: flux is distorted (crowded at one pole tip, weakened at the other) but its average value changes little.
- The terminal voltage drops only slightly (mainly due to and the small quadrature drop). is only a little greater than .
(a) Unity pf load
E
/ |
/ | j I Xs
/ |
O-------+ V
O-------> I (in phase with V)
(ii) Lagging power factor (inductive) load
- For zero pf lagging, the current lags the emf by 90°; armature flux acts directly opposite to the main flux along the pole axis.
- The effect is demagnetising; the resultant air-gap flux and generated voltage fall.
- For a practical lagging pf (e.g. 0.8) the effect is partly cross-magnetising and partly demagnetising.
- The terminal voltage falls considerably with load; , and regulation is large and positive. More field current is needed to keep constant.
(b) Lagging pf load
E
/|
/ | j I Xs
/ |
O------+ V
`-.
`-. I (lags V by phi)
(iii) Leading power factor (capacitive) load
- For zero pf leading, the current leads the emf by 90°; the armature flux acts along the main flux.
- The effect is magnetising (strengthening); the air-gap flux increases.
- The terminal voltage rises with load; can be greater than , so regulation can be negative. Less field current is needed.
(c) Leading pf load
I E
\ /'.
\ / '. j I Xs
\/ '.
O----------+ V
I leads V by phi; E < V
Summary
| Load pf | Nature of armature reaction | Effect on terminal voltage |
|---|---|---|
| Unity | Cross-magnetising (distorting) | Small drop |
| Zero lagging | Purely demagnetising | Large drop () |
| Zero leading | Purely magnetising | Rise () |
| Practical lag/lead | Cross + de-/magnetising | Drop / rise |
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Terminal voltage above emf and armature reaction · Electric Machines II, chapter 1
- Why terminal voltage exceeds emf on capacitive load · Electric Machines II, chapter 1 · asked 3×
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- Load characteristics and capacitive load voltage rise · Electric Machines II, chapter 1 · asked 3×
- Change in emf to raise power factor to unity · Electric Machines II, chapter 1
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Synchronous generator load characteristics, capacitive load · Electrical Machines, chapter 6
- Armature reaction in synchronous generator · Electrical Machine, chapter 6 · asked 2×
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×