Synchronous generator load characteristics, capacitive load
Short answer
With capacitive load, armature reaction is magnetising, aiding the main field flux. The phasor drop jIXs has a component opposing V, so E = V + jIXs yields E < V, making terminal voltage greater than internal emf.
Explain load characteristics of synchronous generator. Why terminal voltage of a synchronous generator is greater than internal generated emf (E) in case of capacitive load? Explain with the help of armature reaction and phasor diagram.
Load characteristics of a synchronous generator
The load characteristic (external characteristic) is the plot of terminal voltage against load current at constant speed, constant field current and constant power factor.
V
| leading pf (rises)
| _.-'
| ______----- unity pf (small fall)
| `-._
| `-._ lagging pf (falls)
+----------------------> I
- Lagging pf (inductive): the armature reaction is demagnetising, and the synchronous impedance drop also reduces the voltage, so falls considerably with load.
- Unity pf: the armature reaction is mainly cross-magnetising; falls slightly.
- Leading pf (capacitive): the armature reaction is magnetising, so rises with load.
Why with capacitive load
The phasor equation for a generator is , where includes the armature reaction reactance ().
- With leading current, the armature flux aids the main field flux (magnetising armature reaction). In the phasor diagram this appears as a reactance drop that acts in the opposite sense to the lagging case.
- The drop leads by , and itself leads , so has a component directed opposite to . In the second term therefore reduces the magnitude, so .
* tip of E
.-' \
.-' \ jIXs (leads I by 90 deg)
.-' E \
.-' \
O------------------------> V
I leads V by phi; E = V + jIXs is shorter than V
Neglecting , with leading by angle (and small compared with ):
The same result is seen physically: the capacitive load current produces a field that adds to the main field, so the net flux (and the terminal voltage) is greater than that due to the field current alone. This is a Ferranti-like voltage rise, and it is why the voltage regulation is negative for leading pf.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Armature reaction in synchronous generator · Electrical Machines, chapter 6
- Synchronous generator working; armature reaction · Electrical Machines, chapter 6
- EMF of short shunt compound generator (0.5 Ω armature) · Electrical Machines I, chapter 3 · asked 2×
- Short shunt vs long shunt generated voltage (150 A, 230 V) · Electrical Machines I, chapter 3
- 30 kW shunt generator: emf, copper loss, efficiency · Electrical Machines, chapter 3 · asked 2×
- 30 kW shunt generator: emf, copper loss, efficiency (100 W) · Electrical Machines, chapter 3 · asked 2×
- Why terminal voltage exceeds emf on capacitive load · Electric Machines II, chapter 1 · asked 3×
- Terminal voltage above emf and armature reaction · Electric Machines II, chapter 1
- Load characteristics and capacitive load voltage rise · Electric Machines II, chapter 1 · asked 3×
- When terminal voltage is less or more than emf · Electric Machines II, chapter 1