Armature reaction in synchronous generator
Short answer
For resistive load, armature reaction is cross-magnetising, distorting flux. Inductive load causes demagnetising reaction, reducing flux. Capacitive load causes magnetising reaction, increasing flux and raising terminal voltage.
Explain the armature reaction in a synchronous generator for resistive, inductive and capacitive loading with necessary diagram.
Armature reaction in a synchronous generator is the effect of the armature mmf (produced by load current) on the main field mmf . Armature current in the three-phase winding produces a field that rotates at synchronous speed, so it is stationary with respect to the rotor poles. The result depends on the angle between the armature current and the induced emf .
1. Resistive load (unity pf)
Current is in phase with . The armature mmf lags by , so it acts across the pole axis.
- Cross-magnetising armature reaction.
- The flux is distorted: the trailing pole tip is strengthened, the leading tip weakened; the net flux is roughly the same (slightly reduced by saturation).
- Terminal voltage drops slightly.
Ff --> Fa (down, 90 deg) Result: Fr = Ff + Fa
N-----S | (shifted)
2. Inductive load (lagging pf)
Current lags by up to . For zero-pf lagging, is directly opposite to .
- Demagnetising (partly cross-magnetising for general lagging).
- Net flux is reduced, so the induced emf falls and drops significantly.
- To keep constant the field current must be increased.
Ff --> <-- Fa (zero pf lag)
Fr = Ff - Fa
3. Capacitive load (leading pf)
Current leads by up to . For zero-pf leading, is in the same direction as .
- Magnetising (partly cross-magnetising for general leading).
- Net flux increases, the induced emf rises, so may exceed .
- The field current must be decreased to hold voltage.
Ff --> --> Fa (zero pf lead)
Fr = Ff + Fa
| Load | Armature reaction | Effect on flux | Terminal voltage |
|---|---|---|---|
| Resistive | Cross-magnetising | Distorted | Slightly lower |
| Inductive | Demagnetising | Reduced | Lower |
| Capacitive | Magnetising | Increased | Higher |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer at resistive, inductive, capacitive loads · Electrical Machines, chapter 2
- Synchronous generator working; armature reaction · Electrical Machines, chapter 6
- Synchronous generator load characteristics, capacitive load · Electrical Machines, chapter 6
- Armature reaction in DC machines and its remedies · Electrical Machines I, chapter 3
- Short note: Armature reaction in dc machine · Electrical Machines, chapter 3
- DC generator types; compound loading characteristics · Electrical Machines, chapter 3
- Armature reaction in synchronous generator · Electrical Machine, chapter 6 · asked 2×
- Armature reaction at different load power factors · Electric Machines II, chapter 1 · asked 7×
- Terminal voltage above emf and armature reaction · Electric Machines II, chapter 1
- MCB types for resistive and inductive loads · Switchgear and Protection, chapter 3