- 2080 Bhadra · 3+5 marks
Terminal voltage above emf and armature reaction
Short answer
Yes, with leading pf loads. Leading current produces magnetizing armature reaction, strengthening the field, so terminal voltage V can exceed generated emf E. With unity pf load, armature reaction is cross-magnetizing causing slight voltage drop; with lagging pf, it is demagnetizing, causing a large voltage drop.
Is it possible that the terminal voltage of synchronous generator (alternator) be greater than internal generated emf? Explain with proper phasor and diagrams. Also describe the effect of armature reaction in resistive and inductive loading with proper diagrams.
Yes. The terminal voltage of an alternator can be greater than the internally generated emf when it supplies a leading power factor (capacitive) load.
Why
The voltage equation is
with for lagging and for leading current. With leading current the term is small, so . Physically, the armature reaction of a leading current is magnetising: it strengthens the main field flux, so the voltage rises with load.
Leading pf load (E < V)
I E
\ /'.
\ / '. j I Xs
\/ '.
O----------+ V
Effect of armature reaction: resistive (unity pf) load
- Current is in phase with emf; armature mmf is at 90° to the field mmf.
- Effect is cross-magnetising: flux is distorted (stronger at one pole tip, weaker at the other) with little change in its total value.
- Terminal voltage falls slightly with load; is a little more than .
Unity pf
E
/ |
/ | j I Xs
/ |
O-------+ V
O-------> I
Effect of armature reaction: inductive (lagging pf) load
- For zero pf lagging, current lags emf by 90°, the armature mmf directly opposes the field mmf.
- Effect is demagnetising; air-gap flux falls and the terminal voltage drops sharply with load.
- For practical lagging pf (e.g. 0.8), it is partly demagnetising and partly cross-magnetising. More field current is needed to hold rated voltage; regulation is large and positive.
Lagging pf (E > V)
E
/|
/ | j I Xs
/ |
O------+ V
`-.
`-. I
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Why terminal voltage exceeds emf on capacitive load · Electric Machines II, chapter 1 · asked 3×
- When terminal voltage is less or more than emf · Electric Machines II, chapter 1
- Armature reaction at different load power factors · Electric Machines II, chapter 1 · asked 7×
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- Load characteristics and capacitive load voltage rise · Electric Machines II, chapter 1 · asked 3×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Armature reaction in synchronous generator · Electrical Machines, chapter 6
- Armature reaction in synchronous generator · Electrical Machine, chapter 6 · asked 2×
- Synchronous generator load characteristics, capacitive load · Electrical Machines, chapter 6
- Synchronous generator working; armature reaction · Electrical Machines, chapter 6