Load characteristics and capacitive load voltage rise
Short answer
Load characteristics show terminal voltage vs. armature current at constant field current. Lagging pf causes a drop, unity pf a slight drop, and leading pf a rise. With a capacitive load, armature reaction is magnetizing, increasing the air-gap flux, so terminal voltage becomes greater than the generated emf E.
Explain load characteristics of synchronous generator. Why terminal voltage of a synchronous generator is greater than internal generated emf (E) in case of capacitive load? Explain with the help of armature reaction and phasor diagram.
Load (external) characteristics
The load or external characteristic of an alternator is the curve of terminal voltage against load (armature) current , at constant speed and constant field current, for a given load power factor.
Vt
| ___.-- leading pf
| ___.--'
|E ------'----------.___ unity pf
| `--.
| `--.__ lagging pf
| `--.__
+--------------------------------> Ia
0 rated Ia
- All curves start at (no load).
- Lagging pf: voltage falls sharply because of the demagnetising armature reaction and the large drop in phase with .
- Unity pf: voltage falls slightly (cross-magnetising effect, and small quadrature drop).
- Leading pf: voltage rises with load because armature reaction is magnetising.
- Hence a lower pf (lagging) gives poorer regulation; an automatic voltage regulator changes the field current to hold constant.
Why for capacitive load
Per phase, and
The reactive term is reduced by the reactance drop, so can be smaller than .
Armature reaction view: with a capacitive load the current leads the emf (by 90° for a pure capacitor). The armature mmf then acts along the axis of the field poles and aids the field flux (magnetising effect). The air-gap flux increases, so the voltage at the terminals is higher than the open-circuit emf produced by the field current alone.
Leading pf phasor diagram
I E
\ /'.
\ / '. j I Xs
\/ '.
O----------+ V (E < V)
Consequence: voltage regulation is negative; less excitation is needed at leading pf, and over-voltage can occur when a lightly loaded long line or capacitor bank is fed.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Why terminal voltage exceeds emf on capacitive load · Electric Machines II, chapter 1 · asked 3×
- Terminal voltage above emf and armature reaction · Electric Machines II, chapter 1
- When terminal voltage is less or more than emf · Electric Machines II, chapter 1
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- Armature reaction at different load power factors · Electric Machines II, chapter 1 · asked 7×
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1
- Internal emf, no-load emf and regulation · Electric Machines II, chapter 1
- Synchronous generator load characteristics, capacitive load · Electrical Machines, chapter 6
- Armature reaction in synchronous generator · Electrical Machines, chapter 6
- Armature reaction in synchronous generator · Electrical Machine, chapter 6 · asked 2×
- Synchronous generator working; armature reaction · Electrical Machines, chapter 6