Synchronous generator working; armature reaction
Short answer
Armature reaction is the effect of stator mmf on the main field flux. For resistive load it is cross-magnetising, for inductive load demagnetising, and for capacitive load magnetising, respectively causing slight drop, large drop, or rise in terminal voltage.
How does three phase synchronous generator work? What do you mean by armature reaction? Comment on the results of different load power factor on armature flux.
Working of a three-phase synchronous generator (alternator)
- The rotor carries a DC-excited field winding (the poles). The prime mover turns the rotor at the constant speed .
- The rotating flux cuts the three-phase armature (stator) windings, which are placed (electrical) apart. By Faraday's law, an emf is induced in each phase:
- The three emfs are equal in magnitude and displaced by in time, giving a balanced three-phase supply.
- When a load is connected, a three-phase armature current flows, and the terminal voltage is .
Armature reaction
Armature reaction is the effect of the armature (stator) mmf, produced by the load current, on the main field flux (its magnitude and distribution). The armature current produces a field rotating at synchronous speed, which is stationary relative to the rotor, and it either opposes, aids or distorts the main flux.
Effect of load power factor
| Load pf | Angle of with | Armature reaction | Effect on flux and |
|---|---|---|---|
| Unity | in phase with | Cross-magnetising | Flux distorted (weakens one pole tip, strengthens the other); slight fall in |
| Zero lagging | lags by | Fully demagnetising | Main flux reduced, falls a lot |
| Zero leading | leads by | Fully magnetising | Main flux increased, rises |
| General lagging | between 0 and | Partly cross, partly demagnetising | falls |
| General leading | between 0 and | Partly cross, partly magnetising | may rise |
Zero pf lagging: Fa opposes Ff Zero pf leading: Fa aids Ff
Ff ---> <--- Fa Ff ---> ---> Fa
Fr = Ff - Fa Fr = Ff + Fa
The armature reaction is represented by a reactance , which together with the leakage reactance gives the synchronous reactance .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Armature reaction in synchronous generator · Electrical Machines, chapter 6
- Synchronous generator load characteristics, capacitive load · Electrical Machines, chapter 6
- Power to 10 Ω load from shunt generator · Electrical Machines I, chapter 3
- Wave-wound shunt generator, power absorbed by load · Electrical Machines, chapter 3
- Armature reaction in DC machines and its remedies · Electrical Machines I, chapter 3
- Short note: Armature reaction in dc machine · Electrical Machines, chapter 3
- Armature reaction in synchronous generator · Electrical Machine, chapter 6 · asked 2×
- Armature reaction at different load power factors · Electric Machines II, chapter 1 · asked 7×
- 3-phase synchronous generator construction · Electrical Machine, chapter 6
- Synchronous generator working principle · Basic Electrical and Electronics Engineering, chapter 2