True/false: load rejection raises terminal voltage
Short answer
TRUE. Sudden load loss eliminates the internal voltage drop, the unloaded line experiences Ferranti rise, and generator overspeed increases emf; together these can raise terminal voltage to about 1.5 pu.
State whether the following statement is TRUE or FALSE. Also give the justification: Load rejection causes the terminal voltage to rise up.
TRUE.
Justification: When a large load is suddenly disconnected (load rejection), the voltage at the generator and line terminals rises, for these reasons:
- Loss of internal voltage drop. The load current had caused a voltage drop across the generator and transformer reactances. After rejection, the terminal voltage rises to about the internal emf (1.1–1.2 pu) until the AVR reduces the excitation.
- Ferranti effect. The long line becomes unloaded, and its charging current raises the receiving-end voltage by the factor (about 9.5% for 400 km at 50 Hz, where ).
- Overspeed. The turbine input cannot be reduced at once, so the generator speeds up. The emf rises roughly in proportion to speed, so the effect is largest for hydro sets, which can overspeed by 30–50%.
- Self-excitation of a generator feeding a long open line can raise the voltage further.
V (pu)
1.5 | __
| / \__
1.0 |__/ \______ (AVR/governor act)
+-----------------> t
^ load rejected
This temporary overvoltage can reach 1.5 pu and last for seconds. It is limited with shunt reactors, fast AVR and governor action, and SVCs.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- True/false: cables suppress switching overvoltage · High Voltage Engineering, chapter 3
- True/false: protective ratio and grounding · High Voltage Engineering, chapter 4
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
- Effect of load rejection · High Voltage Engineering, chapter 3
- Voltage rise at cable–overhead line junction · High Voltage Engineering, chapter 3 · asked 2×
- Voltage build-up at line–cable junction · High Voltage Engineering, chapter 3
- True/False: ampere conductors and temperature rise · Electric Machine Design, chapter 5
- True/false: series motor started at no load · Electrical Machine, chapter 4
- DC series motor started at no load: true/false · Electrical Machines, chapter 4
- T/F: larger conductor raises corona inception voltage · Transmission and Distribution System Design, chapter 4 · asked 2×