TRUE. Protective ratio depends on grounding because arrester rating is chosen based on the coefficient of earthing, which varies with grounding type. Effectively grounded systems allow lower arrester ratings and higher protective ratios.
State whether the following statement is TRUE or FALSE. Also give the justification: Protective ratio depends upon the type of grounding system employed.
TRUE.
Justification
The protective ratio (PR) is the ratio of the equipment insulation level (BIL) to the protective level of the arrester:
The arrester protective level depends on the arrester rating, and the rating depends on how the system neutral is grounded:
- During a line-to-ground fault, the voltage of the healthy phases rises. The arrester must not conduct (and must reseal) at this power-frequency voltage, so its rating is chosen as
where is the coefficient of earthing.
| Grounding type | Coefficient of earthing | Arrester rating |
|---|---|---|
| Effectively grounded | ≤ 0.8 | 80% arrester |
| Non-effectively (resistance) grounded | about 0.8–1.0 | higher |
| Isolated neutral | 1.0 or more | 100% (or more) arrester |
- An effectively grounded system allows a lower-rated arrester with a lower protective level. For the same BIL this gives a higher protective ratio (more margin), or for the same margin it allows a reduced BIL.
- An ungrounded system needs a higher-rated arrester, so the protective level is higher and the protective ratio for the same equipment is smaller.
So the protective ratio obtainable depends on the type of grounding employed. This is why EHV systems are effectively grounded: it permits reduced insulation levels.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- True/false: cables suppress switching overvoltage · High Voltage Engineering, chapter 3
- True/false: load rejection raises terminal voltage · High Voltage Engineering, chapter 3
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
- Improper earthing and system grounding practice · High Voltage Engineering, chapter 2
- True/false: air conditioner is closed loop · Control Systems, chapter 1
- True/false: feedback makes response faster · Control Systems, chapter 1
- True/false: derivative controllers always used with others · Control Systems, chapter 7 · asked 3×
- True/false: CT secondary kept open · Electrical Machine, chapter 2