- 2079 Chaitra · 4+4 marks
Volt-time curve significance and surge arrester
Short answer
The volt-time curve plots breakdown voltage versus time. For coordination, the arrester's curve must be below the insulation's curve with a 15–25% margin at all times, so the arrester always operates first. A surge arrester is a nonlinear device: high resistance normally, it becomes conductive during a surge, clamping voltage and diverting current to earth, then reseals.
Write about significance of volt-time characteristics curve in insulation coordination. Describe general working principle of a surge arrester.
Significance of the volt–time characteristic in insulation coordination
The volt–time (V–t) curve of an insulation or a protective device plots the peak voltage at breakdown (flashover) against the time to breakdown, for impulses of a standard shape but increasing amplitude. With a steeper or higher impulse, breakdown happens sooner and at a higher voltage, so the curve rises at short times.
V |\
| \ equipment insulation (upper)
| \___________________
|\
| \__ protective device (lower)
| \_________________
+-------------------------> t (us)
Significance:
- Basis of coordination. The V–t curve of the protective device (arrester, rod gap) must lie below that of the protected insulation at all times, with a margin of about 15–25%. Then the device always operates first.
- Short-time behaviour. For very steep fronts, a device with a rising V–t curve (such as a rod gap) may operate too late. The curves show whether it gives protection for steep waves.
- Selection of BIL and arrester rating. Comparing the curves fixes the transformer BIL, the arrester protective level and the protective ratio.
- Coordination of different insulations in a substation (bushings, line insulators, breakers) so that flashover, if any, happens at a harmless place.
General working principle of a surge arrester
A surge arrester (lightning arrester) is a non-linear device connected between line and earth near the equipment.
- Normal voltage: the arrester has a very high resistance (series gap open, or a metal-oxide block at low current). Only a tiny leakage current flows.
- Surge arrives: when the voltage exceeds the spark-over (or reference) level, the gap sparks over or the ZnO blocks become highly conductive. The surge current is diverted to earth.
- Clamping: because of the non-linear characteristic (with – for ZnO), the voltage across the arrester (the residual voltage) stays almost constant even for large currents. The equipment sees only this clamped voltage.
- Resealing: after the surge, the voltage returns to normal. The resistance becomes high again and the power-follow current is interrupted (by the gap in gapped types), so the arrester is ready for the next surge.
line ----+---- to equipment
|
[ZnO] non-linear
|
earth
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Volt-time curve and how it is plotted · High Voltage Engineering, chapter 4
- Arrester 100 m from transformer coordination · High Voltage Engineering, chapter 4
- Transformer–arrester coordination expression · High Voltage Engineering, chapter 4
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4
- Arrester coordination for 40 kA discharge · High Voltage Engineering, chapter 4 · asked 2×
- Arrester coordination for 8000 kV strike · High Voltage Engineering, chapter 4 · asked 2×
- Fuse time-current factors and coordination · Switchgear and Protection, chapter 3
- Surge impedance loading and significance · Power System Analysis I, chapter 5 · asked 2×
- Development stages and PRoR working principle · Hydropower Engineering, chapter 2
- Two proportions: mothers working full-time · Probability and Statistics, chapter 7