Capability curve of a generator

Short answer

A capability curve defines the region of active and reactive power a generator can continuously sustain. Limits: armature heating (MVA circle), field heating (over-excited circle), prime mover limit (maximum P), under-excitation limits (steady-state stability and core-end heating), and minimum load. It guides loading and VAr output for voltage control.

What is capability curve of a generator? Describe briefly.

A capability curve (P–Q chart) of a synchronous generator shows the region of active power PP and reactive power QQ in which the generator can operate continuously without exceeding thermal and stability limits. Operators use it to set loading and VAr output.

 Q (lagging, over-excited)
  ^
  |-------._    field heating limit
  |         '.
  |           \
  |            |  <- turbine limit
  |            |     (P = Pmax)
  +------------+---> P
  |            |  <- stator heating
  |           /      limit (circle S)
  |   ______.'
  |  under-excitation /
  |  stability limit
  v
 Q (leading, under-excited)

Limits that form the curve

  1. Stator (armature) current heating limit: P2+Q2=(VIa)2=S2P^2 + Q^2 = (V I_a)^2 = S^2; a circle centred at the origin with radius equal to rated MVA.
  2. Field (rotor) current heating limit: maximum excitation emf EmaxE_{max} gives a circle centred at (0,−V2/Xs)(0, -V^2/X_s) with radius EmaxV/XsE_{max}V/X_s. This limits the lagging (over-excited) region.
  3. Prime mover (turbine) limit: maximum turbine output, a vertical line P=PmaxP = P_{max}.
  4. Under-excitation limits: in the leading region, the steady-state stability limit (δ\delta approaching 90°, with practical margin) and stator end-core heating limit the VAr absorption.
  5. Minimum load limit: some turbines (e.g. Francis) cannot run stably below about 40% load.

Use

  • Rated point lies where the stator circle meets the field circle at rated power factor (e.g. 0.85 lagging).
  • Shows how much reactive power the unit can supply or absorb at a given PP, needed for grid voltage control and for setting AVR limiters (over-excitation and under-excitation limiters).