- 2070 Magh · 10 marks
Power duration curve and primary/secondary energy
Short answer
Installed capacity at 45% exceedance flow (380 m³/s) is 331.8 MW. Primary energy from minimum flow (100 m³/s) is 764.8 GWh/yr; secondary energy 1705.6 GWh/yr from area under the capped power duration curve.
From the following data of flow at a given site for an average year compute and draw a power duration curve. Assume an average net available head of 100 m and a combined turbine generator efficiency of 89%. Determine the primary and secondary energy available during a year if the plant capacity is fixed at power corresponding to the flow available for 45% of time.
| Flow (m³/s) | 900 | 600 | 500 | 450 | 400 | 360 | 340 | 300 | 280 | 200 | 140 | 100 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| % time | 1 | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 93 | 100 |
A power duration curve is the flow duration curve with the flow axis converted to power, . The area under it gives the energy.
Power for each flow
| % time | Q (m³/s) | Power (MW) |
|---|---|---|
| 1 | 900 | 785.78 |
| 10 | 600 | 523.85 |
| 20 | 500 | 436.55 |
| 30 | 450 | 392.89 |
| 40 | 400 | 349.24 |
| 50 | 360 | 314.31 |
| 60 | 340 | 296.85 |
| 70 | 300 | 261.93 |
| 80 | 280 | 244.47 |
| 90 | 200 | 174.62 |
| 93 | 140 | 122.23 |
| 100 | 100 | 87.31 |
P (MW)
786 |*
| \
524 | *
437 | *
393 | *
349 | *
332 |======*===================== <- installed capacity 331.8 MW (Q45)
314 | *
297 | *
262 | * secondary
244 | *
175 | *
122 | *
87 |=====================*===== <- firm power 87.3 MW
| primary (firm)
+------------------------------>
0 45 93 100 % time
Plant capacity (flow at 45% time)
Primary energy
Flow available 100% of the time = 100 m³/s.
Total energy (area under capped curve, trapezoidal rule)
Flow used is capped at 380 m³/s from 0% to 45%.
| Interval (%) | Mean Q used | Δt (%) | Area |
|---|---|---|---|
| 0–45 | 380 | 45 | 17,100 |
| 45–50 | 370 | 5 | 1,850 |
| 50–60 | 350 | 10 | 3,500 |
| 60–70 | 320 | 10 | 3,200 |
| 70–80 | 290 | 10 | 2,900 |
| 80–90 | 240 | 10 | 2,400 |
| 90–93 | 170 | 3 | 510 |
| 93–100 | 120 | 7 | 840 |
| Total | 32,300 |
Mean flow used m³/s.
Plant factor .
Answer: Installed capacity ≈ 331.8 MW; primary energy ≈ 764.8 GWh/yr; secondary energy ≈ 1705.6 GWh/yr.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Primary and secondary energy with 10% environmental flow · Hydro Power, chapter 3
- Primary and secondary energy (102 m head) · Hydro Power, chapter 3
- Primary and secondary energy at 45% exceedance · Hydro Power, chapter 3
- Primary and secondary energy (Nepali calendar months) · Hydro Power, chapter 3
- Primary/secondary energy and pondage volume · Hydro Power, chapter 3
- Firm and secondary energy from average monthly flows · Hydro Power, chapter 3
- Flow duration curve; firm and secondary energy · Hydropower Engineering, chapter 3
- Flow duration curve and power at mean flow · Hydropower Engineering, chapter 3
- Micro hydro net head, power and energy · Energy Resources, chapter 5
- Hydropower site power and turbine · Energy Environment and Society, chapter 3