Short answer

Installed capacity at 45% exceedance flow (380 m³/s) is 331.8 MW. Primary energy from minimum flow (100 m³/s) is 764.8 GWh/yr; secondary energy 1705.6 GWh/yr from area under the capped power duration curve.

From the following data of flow at a given site for an average year compute and draw a power duration curve. Assume an average net available head of 100 m and a combined turbine generator efficiency of 89%. Determine the primary and secondary energy available during a year if the plant capacity is fixed at power corresponding to the flow available for 45% of time.

Flow (m³/s)900600500450400360340300280200140100
% time110203040506070809093100

A power duration curve is the flow duration curve with the flow axis converted to power, P=9.81 QHηP = 9.81\,Q H \eta. The area under it gives the energy.

Power for each flow

P=9.81×Q×100×0.89=873.09 Q kWP = 9.81 \times Q \times 100 \times 0.89 = 873.09\,Q\ \text{kW}
% timeQ (m³/s)Power (MW)
1900785.78
10600523.85
20500436.55
30450392.89
40400349.24
50360314.31
60340296.85
70300261.93
80280244.47
90200174.62
93140122.23
10010087.31
P (MW)
 786 |*
     | \
 524 |  *
 437 |   *
 393 |    *
 349 |     *
 332 |======*=====================  <- installed capacity 331.8 MW (Q45)
 314 |       *
 297 |        *
 262 |          *      secondary
 244 |            *
 175 |               *
 122 |                  *
  87 |=====================*=====  <- firm power 87.3 MW
     |        primary (firm)
     +------------------------------>
     0      45             93  100   % time

Plant capacity (flow at 45% time)

Q45=400−45−4050−40(400−360)=380 m3/sPinst=873.09×380=331,774 kW≈331.8 MW\begin{aligned} Q_{45} &= 400 - \frac{45-40}{50-40}(400-360) = 380\ \text{m}^3/\text{s} \\ P_{inst} &= 873.09 \times 380 = 331{,}774\ \text{kW} \approx 331.8\ \text{MW} \end{aligned}

Primary energy

Flow available 100% of the time = 100 m³/s.

Pf=873.09×100=87,309 kWEp=87,309×8760=764.83 GWh\begin{aligned} P_f &= 873.09 \times 100 = 87{,}309\ \text{kW} \\ E_p &= 87{,}309 \times 8760 = 764.83\ \text{GWh} \end{aligned}

Total energy (area under capped curve, trapezoidal rule)

Flow used is capped at 380 m³/s from 0% to 45%.

Interval (%)Mean Q usedΔt (%)Area
0–453804517,100
45–5037051,850
50–60350103,500
60–70320103,200
70–80290102,900
80–90240102,400
90–931703510
93–1001207840
Total32,300

Mean flow used =32,300/100=323= 32{,}300/100 = 323 m³/s.

Etotal=873.09×323×8760=2470.39 GWhEs=2470.39−764.83=1705.56 GWh\begin{aligned} E_{total} &= 873.09 \times 323 \times 8760 = 2470.39\ \text{GWh} \\ E_s &= 2470.39 - 764.83 = 1705.56\ \text{GWh} \end{aligned}

Plant factor =323/380=85%= 323/380 = 85\%.

Answer: Installed capacity ≈ 331.8 MW; primary energy ≈ 764.8 GWh/yr; secondary energy ≈ 1705.6 GWh/yr.