- 2080 Asoj · 8 marks
Primary and secondary energy at 45% exceedance
Short answer
Plant capacity is 55.9 MW based on flow at 45% exceedance (39.45 m³/s). Primary energy 223.5 GWh/yr from minimum flow 18 m³/s. Secondary energy 192.7 GWh/yr, total 416.3 GWh/yr. Computed using flow duration curve, power equation, and monthly energy summation with 730 hours per month.
The mean monthly flow of a river in Nepal is given in the below table. Calculate the primary and secondary energy that can be generated from the river if the plant capacity is fixed at power corresponding to the flow available for 45% of the time. Consider the plant's overall efficiency as 85% and the Net head as 170 m.
| Months | Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Flow (m³/s) | 30 | 28 | 24 | 29 | 18 | 37 | 65 | 90 | 74 | 56 | 42 | 39 |
Primary (firm) energy is the energy that can be produced all year from the minimum (dependable) flow. Secondary energy is the extra energy produced when flow is above the minimum, up to the plant capacity.
Step 1: Flow duration (Weibull plotting position , N = 12)
| Rank m | Q (m³/s) | % time exceeded |
|---|---|---|
| 1 | 90 | 7.69 |
| 2 | 74 | 15.38 |
| 3 | 65 | 23.08 |
| 4 | 56 | 30.77 |
| 5 | 42 | 38.46 |
| 6 | 39 | 46.15 |
| 7 | 37 | 53.85 |
| 8 | 30 | 61.54 |
| 9 | 29 | 69.23 |
| 10 | 28 | 76.92 |
| 11 | 24 | 84.62 |
| 12 | 18 | 92.31 |
Step 2: Flow at 45% time (linear interpolation)
Step 3: Plant capacity
kW
Step 4: Primary energy (minimum flow 18 m³/s, May)
Step 5: Total energy (flow used = smaller of Q and 39.45; 730 h per month)
| Month | Q | Q used | Power (kW) |
|---|---|---|---|
| Jan | 30 | 30 | 42,526 |
| Feb | 28 | 28 | 39,691 |
| Mar | 24 | 24 | 34,021 |
| Apr | 29 | 29 | 41,109 |
| May | 18 | 18 | 25,516 |
| Jun | 37 | 37 | 52,449 |
| Jul–Nov | ≥ 42 | 39.45 | 55,922 each |
| Dec | 39 | 39 | 55,284 |
m³/s-months.
Answer: Plant capacity ≈ 55.9 MW; primary energy ≈ 223.5 GWh/yr; secondary energy ≈ 192.7 GWh/yr (total ≈ 416.3 GWh/yr).
(If is used for the duration curve, m³/s and the secondary energy rises slightly; the method is the same.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Power duration curve and primary/secondary energy · Hydro Power, chapter 3
- Primary and secondary energy with 10% environmental flow · Hydro Power, chapter 3
- Primary and secondary energy (Nepali calendar months) · Hydro Power, chapter 3
- Primary and secondary energy (102 m head) · Hydro Power, chapter 3
- Primary/secondary energy and pondage volume · Hydro Power, chapter 3
- Annual firm and secondary energy (900 m³/s, Nov 650) · Hydro Power, chapter 3 · asked 2×
- Flow duration curve; firm and secondary energy · Hydropower Engineering, chapter 3
- RoR best installed capacity (NRs, 45 years) · Hydropower Engineering, chapter 3
- Monthly energy loss in four secondary lines · Transmission and Distribution System Design, chapter 7
- Installed capacity, energy and daily peaking reservoir (2079) · Hydropower Engineering, chapter 3 · asked 2×