Grounded versus ungrounded systems

Short answer

A grounded system holds neutral near earth, healthy phases stay near phase voltage, suppresses arcing overvoltages, provides selective relaying with large fault current, but trips on first fault. An ungrounded system has no intentional earth connection, healthy phases rise to line voltage, suffers transient overvoltages up to6 pu, fault detection difficult, but can continue with a single line-to-ground fault.

Compare grounded and ungrounded power system.

A grounded system has its neutral connected to earth (solidly or through an impedance). An ungrounded (isolated neutral) system has no intended connection to earth; it is only coupled to earth through the line-to-ground capacitances.

Comparison

PointGrounded systemUngrounded system
Neutral potentialHeld near earthFloats; can shift
Healthy-phase voltage during L-G faultNear phase voltage (solid)Rises to line voltage (3\sqrt{3} times)
Arcing-ground overvoltagesSuppressedCan reach 5–6 pu, damaging insulation
Earth-fault currentLarge enough to trip relaysSmall capacitive current (3IC03I_{C0})
Fault detectionEasy, selective earth-fault relaysDifficult; only alarm via voltage relays
Insulation levelGraded insulation; cheaper equipmentFull line-voltage insulation needed
Continuity of supplyFaulted section trips at onceCan run with one earth fault for a while
SafetyBetter; touch voltage cleared fastSecond fault can be dangerous
Lightning arrestersLower-rated arresters can be usedHigher rating needed
InterferenceEarth-fault current may disturb telecomLittle
Typical useModern systems, generators, above 33 kVOld small systems, some industrial LV

Capacitive current in an ungrounded system

When one phase is earthed, the other two line capacitances charge to line voltage. The fault current is

If=3 ωC0 VphI_f = 3\,\omega C_0\,V_{ph}

At fault currents above about 4–5 A this capacitive current causes arcing grounds: the arc repeatedly strikes and extinguishes, building up voltage on the healthy phases.

Conclusion for practice

Almost all modern power systems are grounded. The method depends on voltage level: solid for LV and EHV, resistance/reactance for MV, and high-resistance for unit-connected generators.