Electrical characteristics of a unit transformer
Short answer
Rated MVA ≥ generator rating; LV voltage = generator voltage, HV = grid voltage; vector group YNd11 to block zero-sequence; impedance 8–14% for fault/stability; HV taps for voltage control; low losses capitalised; insulation and temperature rise per IEC 60076; cooling ONAN/ONAF or OFWF; overfluxing capability; short-circuit withstand for 2 s.
Discuss electrical characteristics of unit transformer that to be considered during its selection.
The unit transformer (generator step-up transformer of a unit) connects a generator to the HV system. Its electrical characteristics must suit both the generator and the grid.
Electrical characteristics considered
- Rated MVA: at least the generator rated MVA (e.g. 15 MVA for a 12.75 MW, 0.85 pf unit); some margin for overload and the unit auxiliary load.
- Voltage ratio: LV equal to generator voltage (e.g. 11 kV); HV equal to grid voltage plus margin for line drop (e.g. 132 kV).
- Vector group: YNd11 is common: delta on generator side blocks zero-sequence and third harmonics; star-earthed HV gives an earthed system.
- Percentage impedance: about 8–14%. Higher impedance reduces fault level and breaker rating; lower impedance improves voltage regulation and stability. Fixed by fault-level and stability studies.
- Tappings: off-circuit taps (e.g. ±2 × 2.5%) or OLTC on HV, to match grid voltage and control VAr flow.
- Losses and efficiency: no-load (iron) and load (copper) losses are capitalised; low losses save energy for 30+ years.
- Insulation level (BIL) and temperature rise: HV BIL as per insulation coordination; temperature rise per IEC 60076 (oil 60 K, winding 65 K); altitude correction above 1000 m.
- Cooling: ONAN/ONAF for outdoor; OFWF in underground powerhouses.
- Overfluxing capability: must withstand V/Hz rise on load rejection (e.g. 1.1 p.u. continuous, 1.4 p.u. for a few seconds).
- Short-circuit withstand: thermal and dynamic for 2 s per IEC 60076-5.
- Magnetising inrush and noise level.
- Standards: IEC 60076.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer protection, selection and vector group · Power Plant Design, chapter 4
- Unit generator-transformer schemes · Power Plant Design, chapter 4 · asked 3×
- Hydropower site selection factors · Power Plant Design, chapter 3
- Criteria for turbine selection · Power Plant Design, chapter 3 · asked 3×
- Turbine selection method and governing factors · Power Plant Design, chapter 3 · asked 3×
- Design: 550 m head plant, transformer quotation · Power Plant Design, chapter 4 · asked 3×
- Motor selection characteristics; rheostatic and regenerative braking · Utilization of Electrical Energy, chapter 2
- Pump characteristics, losses and selection · Fluid Machines, chapter 4
- Fuse selection for 250 kVA transformer · Switchgear and Protection, chapter 3
- Transformer selection for apartment, residence, industry · Industrial Power Distribution and Illumination, chapter 4