Define coincidence factor
Short answer
Coincidence factor is group maximum demand divided by sum of individual maximum demands (≤1). It prevents oversizing of distribution transformers and feeders by recognizing that individual peaks do not occur simultaneously, allowing accurate equipment rating.
Define coincidence factor with respect to distribution consumer characteristics and discuss its significance on the design of distribution system.
Coincidence factor is the ratio of the maximum demand of a group of consumers taken together to the sum of the individual maximum demands of those consumers:
It is less than 1 because consumers do not all reach their own peaks at the same time. For example, if 50 houses each have a peak of 2 kW but the group peak is 60 kW, the coincidence factor is .
Significance in distribution design:
- The peak load on a distribution transformer, LT feeder or service main is found as (number of consumers) × (individual peak) × (coincidence factor). Without it, equipment would be badly oversized.
- It decreases as the number of consumers increases, so a transformer serving many consumers needs less capacity per consumer than a service drop serving one.
- It lets the designer choose smaller, cheaper transformers and conductors while still meeting the actual peak, and gives realistic voltage drop and loss calculations.
- Wrong (too high) values give idle capacity and high no-load losses; too low values cause overloading.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Define responsibility factor · Transmission and Distribution System Design, chapter 6 · asked 2×
- Define coverage factor · Transmission and Distribution System Design, chapter 6 · asked 2×
- Define loss of load factor · Transmission and Distribution System Design, chapter 6 · asked 2×
- Define consumption growth factor · Transmission and Distribution System Design, chapter 6
- Peak load, load factor and energy from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- Radial vs loop distribution system · Transmission and Distribution System Design, chapter 5 · asked 2×
- T/F: lightning overvoltage in distribution system · Transmission and Distribution System Design, chapter 3
- Distribution system used in INPS · Transmission and Distribution System Design, chapter 5
- Design steps and criteria of distribution system · Water Supply Engineering, chapter 7 · asked 3×
- Pitch factor, distribution factor and EMF equation · Electric Machines II, chapter 1 · asked 3×
- Gumbel's distribution and frequency factor derivation · Engineering Hydrology, chapter 6
- Carry over factor and distribution factor · Theory of Structures II, chapter 3
All Transmission and Distribution System Design chapter 6 questions →