Compute LF = 74/(10×24) = 0.3083 and LLF = 444/(10²×24) = 0.185. Then K1 = (LLF − LF²)/(LF − LF²) = 0.4217, K2 = 1 − K1 = 0.5783. The result is K1 ≈ 0.42, K2 ≈ 0.58.

Using equation LLF = K1×LF + K2×LF², compute the appropriate value of K1 and K2 of system having following load pattern.

Time (hrs)0:00-6:006:00-10:0010:00-14:0014:00-18:0018:00-21:0021:00-24:00
Demand (MW)0422104

The loss of load factor (LLF) is the ratio of the average power loss to the power loss at peak load over a period. Since loss is proportional to the square of load (at constant voltage and power factor):

LLF=∑Pi2tiPmax2 T,LF=∑PitiPmax TLLF = \frac{\sum P_i^2 t_i}{P_{max}^2 \, T}, \qquad LF = \frac{\sum P_i t_i}{P_{max} \, T}

The empirical relation is LLF=K1 LF+K2 LF2LLF = K_1 \, LF + K_2 \, LF^2 with K1+K2=1K_1 + K_2 = 1 (so that LLF = 1 when LF = 1). Two equations are thus available to find K1K_1 and K2K_2.

Step 1: Tabulate the load pattern

Intervaltit_i (h)PiP_i (MW)PitiP_i t_i (MWh)Pi2tiP_i^2 t_i
0–66000
6–10441664
10–1442816
14–1842816
18–2131030300
21–24341248
Total2474444

Peak demand Pmax=10P_{max} = 10 MW, T=24T = 24 h.

Step 2: Load factor

LF=7410×24=0.30833LF2=0.09507\begin{aligned} LF &= \frac{74}{10 \times 24} = 0.30833 \\ LF^2 &= 0.09507 \end{aligned}

Step 3: Loss of load factor

LLF=444102×24=4442400=0.185LLF = \frac{444}{10^2 \times 24} = \frac{444}{2400} = 0.185

Step 4: Solve for K1 and K2

Put K2=1−K1K_2 = 1 - K_1:

LLF=K1LF+(1−K1)LF2K1=LLF−LF2LF−LF2=0.185−0.095070.30833−0.09507=0.089930.21327=0.4217K2=1−0.4217=0.5783\begin{aligned} LLF &= K_1 LF + (1 - K_1) LF^2 \\ K_1 &= \frac{LLF - LF^2}{LF - LF^2} \\ &= \frac{0.185 - 0.09507}{0.30833 - 0.09507} = \frac{0.08993}{0.21327} \\ &= 0.4217 \\ K_2 &= 1 - 0.4217 = 0.5783 \end{aligned}

Check: 0.4217×0.30833+0.5783×0.09507=0.1300+0.0550=0.1850.4217 \times 0.30833 + 0.5783 \times 0.09507 = 0.1300 + 0.0550 = 0.185 ✓

Answer: K1≈0.42K_1 \approx 0.42, K2≈0.58K_2 \approx 0.58, i.e. LLF=0.42 LF+0.58 LF2LLF = 0.42\,LF + 0.58\,LF^2 for this system.

The commonly used Buller–Woodrow values are K1=0.3K_1 = 0.3, K2=0.7K_2 = 0.7; this load pattern (a sharp evening peak with zero load at night) gives a somewhat larger K1K_1. The value of LLF (0.185) lies between LF2LF^2 (0.095) and LFLF (0.308), as it must.