300 kVA transformer efficiency calculation

Short answer

Full-load efficiency at 0.8 lagging pf is98.24%. Maximum efficiency occurs at254.56 kVA, yielding98.26% at0.8 pf.

A 300 kVA single phase transformer has iron losses of 1.8 kW. The full load copper losses is 2500 watts. Calculate, (i) Efficiency at full load, 0.8 lagging pf (ii) kVA supplied at maximum Efficiency (iii) Maximum Efficiency at 0.8 lagging pf.

Given: S=300S=300 kVA, Pi=1.8P_i=1.8 kW, full-load Pcu=2.5P_{cu}=2.5 kW.

(i) Full-load efficiency at 0.8 lagging pf.

Output=300×0.8=240 kW\text{Output}=300\times0.8=240\ \text{kW} Total loss=1.8+2.5=4.3 kW\text{Total loss}=1.8+2.5=4.3\ \text{kW} η=240240+4.3×100=98.24%\eta=\frac{240}{240+4.3}\times100=98.24\%

(ii) kVA at maximum efficiency. Efficiency is maximum when copper loss = iron loss:

x=PiPcu=1.82.5=0.8485x=\sqrt{\frac{P_i}{P_{cu}}}=\sqrt{\frac{1.8}{2.5}}=0.8485 kVA=300×0.8485=254.56 kVA\text{kVA}=300\times0.8485=254.56\ \text{kVA}

(iii) Maximum efficiency at 0.8 pf. Output =254.56×0.8=203.65=254.56\times0.8=203.65 kW. At this load, the copper loss equals the iron loss =1.8=1.8 kW, so the total loss is 2×1.8=3.62\times1.8=3.6 kW:

ηmax=203.65203.65+3.6×100=98.26%\eta_{max}=\frac{203.65}{203.65+3.6}\times100=98.26\%

Answer: (i) 98.24%, (ii) 254.56 kVA, (iii) 98.26%.