- 2068 Shrawan · 8 marks
Star alternator supplying delta load (8+j6)
Short answer
Load branch current = 23 A. Power consumed = 12.7 kW. Power factor = 0.8 lagging. Reactive power = 9.52 kVAR.
A star connected alternator supplies a delta connected load. The impedance of the load branch is (8 + J6)Ω. The line voltage is 230 volt. Determine: i) Current in the load branch ii) Power consumed by the load iii) Power factor of the load iv) Reactive power of the load
The alternator is star connected, but the load is delta connected, so the line voltage across each load branch is V_L = 230 V (phase voltage of load = line voltage).
Z_ph = 8 + j6 = 10∠36.87° Ω
i) Current in the load branch
I_ph = V_L/Z = 230/10 = 23 A (line current = √3 × 23 = 39.8 A)
iii) Power factor
cos φ = R/Z = 8/10 = 0.8 lagging
ii) Power consumed
P = 3 I_ph² R = 3 × 23² × 8 = 12 696 W ≈ 12.7 kW
Check: √3 V_L I_L cos φ = 1.732 × 230 × 39.84 × 0.8 = 12.7 kW.
iv) Reactive power
Q = 3 I_ph² X = 3 × 23² × 6 = 9522 VAR ≈ 9.52 kVAR (lagging)
Apparent power S = √(12 696² + 9522²) = 15.87 kVA.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8
- Delta load (15+j20) phase and line currents · Basic Electrical Engineering, chapter 8
- Delta load phase currents, power, line currents · Basic Electrical Engineering, chapter 8
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Delta load line currents and power, ABC sequence · Basic Electrical Engineering, chapter 8
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- 230/2300 V transformer with load impedance · Electrical Machine, chapter 2
- 230/2300 V transformer with load impedance · Electrical Machines, chapter 2
- Two-wattmeter method star load · Basic Electrical and Electronics Engineering, chapter 1